MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

When Does a Room Trigger NFPA 13 vs. NFPA 13R?

9/9/2025

11 Comments

 
When does a Community Room trigger the need to use NFPA 13 as opposed to NFPA 13R?

If the first floor of a 3-story apartment building is a meeting room, does the building, or perhaps the first floor need to meet NFPA 13?
Picture
​Thanks in advance.

​Sent in anonymously for discussion. Click Title to View | 
Submit Your Question | Subscribe
11 Comments
Kyle
9/9/2025 08:46:53 am

The best guidance I've found on this topic comes from the IBC commentary related to section 903.3.1.2.

Mixed occupancy buildings containing Group R occupancies are permitted to be provided with an NFPA 13R sprinkler system so long as the other occupancies present do not require the building be provided with a sprinkler system in accordance with NFPA 13. The areas not classified as Group R must be provided with protection in accordance with NFPA 13.

The example you provided appears to be nonseparated mixed use A-3/R-2. The presence of a Group R fire area requires the building be provided with a sprinkler system throughout per 903.2.8 and 903.3.1.2 permits use of an NFPA 13R system.

The A-3 occupancy is not required to be provided with sprinkler protection per 903.2.1.3. If the A-3 occupancy/fire area had been required to be provided with sprinkler protection in accordance with NFPA 13, then the entire building would need to be designed to NFPA 13.

In short the building must be provided with a sprinkler system throughout. The Group R-2 areas (2nd and 3rd floors) may be protected in accordance with NFPA 13R while the A-3 (first floor) must be protected in accordance with NFPA 13.

Reply
Brett
9/9/2025 10:56:35 am

I disagree with not sprinklering the assembly occupancy.

From 903.2.8 of the 2021 IBC (capitalized emphasis my own):

"An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all BUILDINGS with a group R fire area."

If the building has a group R fire area then the whole building has to be sprinklered, not just the residential occupancy. The only way around this is with the use of a fire wall to create separate buildings. Obviously that's not an option here.

If the first floor is not appropriately separated from the other two floors then the whole building is required to be sprinklered per NFPA 13 since 13R cannot be used for assembly or business occupancies. I include business because that looks like a small space that might qualify as a business occupancy.

The common way around this is to separate the assembly/business occupancy with a two hour horizontal separation and sprinkler the top floors per NFPA 13R and the bottom floor (combustible concealed spaces included) per NFPA 13. The commentary posted above by Kyle supports this approach.

Reply
Connor
9/10/2025 03:55:49 pm

To clarify, I don't think he's saying the Group A-3 does not need to be sprinklered, but rather that the A-3 portion does not exceed the threshold to require sprinkler and is therefore not the driving requirement. If the A-3 exceeded the threshold in Chapter 9 to require sprinkler, NFPA 13 would apply throughout the building.

As the threshold to sprinkler A-3 is not exceeded, the building is still sprinklered throughout due to the presence of the Group R, but only the A-3 area must meet NFPA 13 requirements. The remainder of the building can meet 13R.

Jesse
9/9/2025 08:53:54 am

Yep what Kyle said. But always check with your AHJ. We hada similar issue in my area where the AHJ amended that section of the IBC to require full 13.

Reply
Anthony
9/9/2025 09:27:46 am

I'd say the common area falls under the exceptions in 6.2.2.2 (13R-16) specifically:
(5) Lounges
(8) Other areas with fire loads similar to residential fire loads.
Along with 7.2.4 referencing 6.2.2.2 and describing design discharge criteria.


There is no storage and a relatively open area. The shown pool table, I would think, would have a similar fire load to a bed/dresser set.

Thus you could remain in 13R and not have to protect your attic ect.

Reply
Jack G
9/9/2025 09:30:53 am

There is a 13 v 13r v 13 d chart in IBC commentary and Myerfire.
How it is built determines how you protect it.
Example
Under area increases , area increases - no 13 r or d.
Reductions - no 13r/d for separated occupancies, type V A Construction ( 5b limited to 2 story)
And a bunch other. ( no manual fire alarms ,no 13 d)
You would have to identify the rated partitions to determine. Also if the area increased due to protecting it with sprinklers .
So in short—- how it is built determines 13, 13r, 13d,
And cannot say without this information.

Reply
Jose R Figueroa
9/9/2025 09:55:05 am

Your building is a low-rise structure. Use NFPA 13R and consult your AHJ. Using NFPA 13 will not significantly increase costs.

Reply
Anthony
9/9/2025 09:59:24 am

Respectfully using full 13 will increase costs significantly assuming you'll most likely have a dry system for the attic.

Reply
Wes
9/9/2025 11:00:32 am

Second this; even for lowrises the combustible concealed spaces and attics can make a major difference in net cost.

Taylor Jenkins
9/9/2025 07:43:56 pm

Check with your local amendments also. In Mass, if the building is classified as a "mixed-use" and contains any "Group R" occupancy, the entire building must be provided with sprinkler protection, regardless of fire areas, size of each occupancy, etc...

We also have an amendment that if the Gross area of the building is over 12,000 sf, the system can no longer be designed to 13R and must meet 13, regardless of occupancy classification..

Reply
Todd Wyatt
9/10/2025 08:54:15 am

The scoping Code (e,g, IBC-2024) determines WHERE an automatic sprinkler system (ASPS) is required :

IBC-2024
Chapter 9 Fire Protection and Life Safety Systems
Section 903 Automatic Sprinkler Systems
903.2 Where Required
Assembly
Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12.
903.2.1 Group A
903.2.1.3 Group A-3
An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
1. The fire area exceeds 12,000 square feet (1115 m2).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.

If Story 01 is classified as a Group A-3 Assembly Occupancy Classification (OC) AND it meets (1) of the (3) above requirements, then this story is required to be protected by a NFPA 13 ASPS.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT