Renovating an 11-story hotel using residential sprinklers in accordance with NFPA 13 (2019).
Calcs based upon S x L (4 sprinklers at .10 density) or manufacturer data sheets (which ever requires greater demand). Sprinklers need to be 175° due to less than 24" from the side of the wall mount diffuser. There are a few rooms that require a SW throw of 20'-4" (22'-0' per data sheets). However, many manufacturers do not manufacturer this 22 ft throw in 175°, only 155°. Can I use a quick response (Viking VK630) SW that throws 22 ft along with the residential sprinklers in the same compartment? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Pete H
5/8/2025 06:20:56 am
I don't see a specific code restriction in 2019 to prevent this (provided the residential head is quick/fast response, if the residential head is not quick/fast response, you've found a magical standard response residential head I've never heard of before.)
Reply
Ed T
5/8/2025 08:20:34 am
NFPA 13, 2019 12.1.4 states that if residential sprinklers are installed in a compartment, all sprinklers within the compartment shall be residential sprinklers
Reply
Jesse
5/8/2025 08:31:16 am
I would say no based upon 2019 NFPA 13 12.1.4
Reply
Jonathan W.
5/8/2025 08:57:09 am
Aside from the code requirements, I believe it's important to understand Residential Sprinklers are designed differently and are tested to meet specific life safety criteria. This includes spray pattern, compartment tenability levels (oxygen, temperature, carbon monoxide), and response element. Residential Sprinklers are designed to wet the walls VS providing a water density at the floor level. They are designed to enhance the survivability within the room of origin compartment.
Reply
Casey Milhorn
5/8/2025 08:59:38 am
I would advise doing anything you can to get that separation and use that 155, otherwise you will need to use QR light hazard sprinklers, which then kicks you out of the 4 head design.
Reply
Jack G
5/8/2025 09:03:37 am
The sprinklers within a room must have the same response time so no. 2019 NFPA-13: 9.4.3.2.
Reply
Jose R Figueroa
5/8/2025 12:32:22 pm
155°F Quick response is acceptable. I don’t see any restriction in NFPA 13 2025.
Reply
O.P.
5/8/2025 02:30:51 pm
Thanks all for the responses - UPDATE - I missed NFPA 2019 12.1.4 that many had referenced - I mistakenly got caught up in 12.1.2 and A12.1.6.1- Interestingly enough, I also made the mistake of looking for a 5.8 or larger orifice SW to throw the 22 ft in 175° temp. I should not have limited my search by orifice. Viking residential SW VK486 9 4.0 k) throws 22 ft , 175° with less psi / gpm than the larger orifices. Todays lesson - slow down
Reply