MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Use Main Drain for Forward-Flow? What to Test?

2/11/2025

12 Comments

 
Forward Flow Test Confusion... I have an NFPA 13R system built in 2013 that doesn't have any hose connection(s) for forward flow testing. The sprinkler contractor is saying they're unable to conduct the test.

I am attempting to understand the codes around this topic and ran into several questions.

First
, NFPA 25: 2020 NFPA 25 13.7.2.3 states, "Where connections do not permit verification of the forward flow test at the minimum flow rate of system demand, tests shall be conducted at the maximum flow rate possible."

Can someone please explain what this means exactly?

My second question
concerns using the main drain to conduct the forward flow test if it's sized appropriately. A previous Meyer Fire blog post, "Solutions for the Overlooked Forward Flow Test," Option 4, mentioned the 2016 NFPA 13 A8.16.2.4.2, but I cannot find that section in the 2019 version.

Has this method changed somehow?

Can the sprinkler contractor use the main drain as a means to conduct the forward flow test?

If so, what else does the AHJ need to know?

Calcs to prove drain size can flow system demand? Pitot reading?

Thank you for reading and I'd love to find some clarity.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Dan Wilder
2/11/2025 08:02:42 am

Couple items:

NFPA 13R in 2013 did not have a requirement for forward flow testing of a backflow, that was added in 2016

If there is no means to forward flow test the backflow, any available means to test the backflow (i.e. main drain) shall be used and recorded.

The Annex section was incorrectly removed in the 2019 rewrite and then added back for the 2022 edition.

Yes, a contractor can (use main drain) to provided the results are documented and the test procedures are generally equal (for most of my local AHJ's). Use of a stream straightener is highly recommended. Calc's may get you close to a proof for equivalency but doing the test is still required so why waste the time?

If there is a large enough issue (AHJ or Insurance is pushing back on the lack of forward flow) just propose the addition of a couple mech tee's and some hose valves within the room or add a bypass at the FDC (if accessible) and this solves all those issues. Remember, the test is only for system demand and does not include hose allowance.

Reply
Anthony
2/11/2025 08:12:17 am

I agree with Dan here. There is no cause to update a system to allow for new testing requirements. Just use the main drain to prove the system is able to achieve full flow through the drain piping.

If I was a cynic, I'd say this is a someone looking for a billable deficiency.

Reply
Joe Meyer
2/11/2025 08:14:47 am

FWIW, I can validate that this is an AHJ asking for advice on how it's proven and not a sprinkler contractor. : )

Anthony
2/11/2025 09:39:59 am

A curve at the riser can always be established with the K factor on the inspector's test and the static at the riser. This works best if there is a test and drain right at the riser. all you'd have to do is read the pressure gauge while the insp test is flowing and use the K factor formula to get your flow. it's not perfect but it's a start.

Brian
2/12/2025 04:39:12 pm

Thank you for the info and just wanted to ask one follow up question. The code says if there are no available test connections, then "tests shall be conducted at the maximum flow rate possible". Does this imply that if the main drain is unable to meet system demand, then no further action is needed as it was tested at the maximum possible flow rate?

Reply
Jonathan Griffin link
2/11/2025 09:47:32 am

One can also insert a Pitot at the 2" Main Drain outfall and obtain a reading... there is a chart available that provides GPM flow from a 2" pipe, as well as software that can provide flow from the 2" piping. (The NFPA 291 formula also works here).

Good Luck!

Reply
Chad
2/11/2025 12:01:12 pm

"Where connections do not permit verification of the forward flow test at the minimum flow rate of system demand, tests shall be conducted at the maximum flow rate possible."

On a 2013 13R that is going to be the main drain, unless there are standpipes/roof hydrant. They can run hoses outside off the standpipes.

Reply
Randy Kimbro
2/11/2025 01:08:46 pm

From an AHJ perspective, the spirit of the forward flow test is to annually exercise all backflow devices/valves to their full open position and ensure the water flowing can meet the GPM for the defined system demand as listed on the hydrostatic data plate. If there is no way to flow that amount of water (we have one riser in a basement that would require 3-400 feet of hose to reach the outside), the main drain can be used as a base measurement of GPM. Whatever test method is approved by the AHJ, it should be repeated the same way annually.

Our tests always include pitot readings which we record every year.

Although NFPA 13R did not include this until 2016 as Dan mentioned, NFPA 13 included this at least from 2007. Dan was incorrect on the hose allowance. NFPA 13 (2019 and 2022)
6.10.2.5.2 The minimum flow rate tested in 6.10.2.5.1 shall be the system demand, including hose stream demand where applicable.

Bottom line from an AHJ, we want to ensure annually, that the sprinkler system can supply the engineered GPM flow in case of a fire.

Reply
Dan Wilder
2/11/2025 04:54:27 pm

The question was a 13R system installed in 2013 and there is no provision in 13R through the 2025 edition to include hose stream, it only references "system demand". I didn't want to introduce extra info that can be confusing for the OP.

Reply
Brian
2/12/2025 04:45:13 pm

I appreciate the info. So if the main drain was not able to flow the system demand, could you then require test connections be added to provide verification of the flow?

Reply
Jeff Ayers
2/12/2025 10:44:54 am

A remote head test was used on one of my projects for the forward flow test. We actually removed the head and connected to the 1 1/4" branch line

But the option we chose on the next project (6 level Multi family Type IIIA with NFPA 13) was to use the roof FHV.

It was nearly as far (remote) as the most remote head, but it was at the highest elevation, providing a more stringent test.

Flowing water through a 2 1/2" FHV on the roof proved to be a very successful test.

Reply
Jack G
2/12/2025 05:20:26 pm

If you doubt that the test and drain and piping isn’t large enough to forward flow the 13r water requirement for the system just install a space for a “ test meter) that will actually measure the flow. Then return pipe you removed. (

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT