I have a requirement from a client to use K25.2 sprinklers on a building up to 50-ft in height.
The design criteria that is provided under NFPA 13 is 12 K25.2 sprinklers at 50 psi, but this criteria is not available in Chapter 13 of NFPA 13. Does anyone know where this came from, or whether it's appropriate? It's for up to a 50-ft roof for protection of cartoned, non-expanded Group A plastics. Thank you. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Mark Fessenden
2/17/2025 08:05:04 am
It’s from FMDS 8-9.
Reply
Ed Dunn
2/17/2025 09:45:45 am
Try VK 514 K-28 Specific Application
Reply
Todd E Wyatt
2/17/2025 08:56:29 am
“K25.2” is referenced in Table 20.17.2.2.3 …
Reply
Mike F
2/17/2025 09:34:12 am
Can the OP provide some more details?
Reply
Jack G
2/17/2025 10:01:16 am
Yes FM 8-9, Vikings is approved to 55 feet, (9) sprinklers at 80 psi.
Reply
Franck
2/17/2025 10:22:07 am
No, it's not appropriate.
Reply
Jose R Figueroa
2/17/2025 11:57:27 am
Frank & Dunn responses are correct. Please refer to FM DS8-9.
Reply
Daniel Contreras
2/17/2025 04:11:56 pm
Jose,
Joe Meyer (moderator)
2/17/2025 11:00:51 am
Just a friendly reminder for all comments - All comments are reviewed. Comments which do not contribute, are not relevant or are disrespectful in nature will be removed.
Reply