Use ESFR Sprinklers Under Sloped Conveyor?

12/8/2025

12 Comments

 
Do we have to use ESFR sprinklers under conveyors, which have slope, solely because the roof system is ESFR?

What code basis—if any—would actually require ESFR protection under conveyors in this situation?

I am currently designing a sprinkler system renovation on a package sorting facility that we did the original conveyor design on 4 years ago. The existing 500,000 sqft open warehouse had (13) k-22 ESFR systems that we did not design. I designed all the systems for the catwalks, mezzanines, and under conveyors using Standard 5.6k quick response, standard spray sprinklers (Reliable RA1425) with shielding under open grate flooring.

The new systems all have their own risers coming off the existing 10" manifolds. It was all hydraulically calculated and approved by the city.

Now we are designing / renovating the conveyor systems because the client added, removed & moved a bunch of conveyors. I removed all sprinklers and pipe from the areas being changed, and most of the new or changed areas we able to reuse existing outlets that we had demolished pipe from. We used the same pipe sizing scheme, same type of sprinklers, and redid all hydraulic calculations.

BUT now the plan reviewer is rejecting the plans citing:

THE SPRINKLER PROTECTING THE BUILDING ARE CLASSIFIED AS ESFR, THE SPRINKLER PROTECTING THE AREA UNDER THE CONVEYORS SHALL BE OF THE SAME TYPE AS PER NFPA 13, 2019, SECTION 9.5.5.3.3.

I responded with NFPA 13 20.6.2, ESFR are only approved to a slope of 2:12 and most of the conveyors are way past that; and noted again that that the existing system is 5.6k.

To which he responded:

THE SPRINKLER PROTECTING THE BUILDING ARE CLASSIFIED AS ESFR, THE SPRINKLER PROTECTING THE AREA UNDER THE CONVEYORS SHALL BE OF THE SAME TYPE AS PER NFPA 13, 2019, SECTION 9.5.5.3.3 WE DO NOT UNDERSTAND THE RESPONSE TO THIS COMMENT, SECTION 20.6.2, WHICH ADDRESSED THE SLOPE OF THE ROOF NOT THE PROTECTION UNDER THE CONVEYOR. INDICATE WHICH STANDARD ADDRESSES THE HYDRAULIC CALCULATION FOR PROTECTION UNDER A CONVEYOR, WE CAN’T FIND THE SPECIFIC DESIGN CRITERIA FOR PROTECTION UNDER THE CONVEYOR USING ESFR SPRINKLERS. UNLESS THE SAME CRITERIA US FOR THE ROOF SYSTEM WILL APPLY UNDER THE CONVEYOR.

Has anyone ever run into this?

If have to use k-22 ESFR, it would be disastrous to the calcs, not to mention the existing system I am coming off of. Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Brett
12/8/2025 06:57:25 am

Your previous designs should have used ESFR sprinklers under those conveyors because there was no other option in previous editions of NFPA 13, but the 2025 edition of NFPA 13 has other options.

Read section 14.2.10.3.7 of the 2025 edition of NFPA 13. If there is no high piled storage under the conveyors then you can use quick response sprinklers and design the system to protect only the area under the conveyors.

Reply
Joe Bergstrom link
12/8/2025 08:46:20 am

There is no storage at all under the conveyors, catwalks or mezzanines. I have done MANY other package sorting facilities like this for different Corporations, in different states & cities, some were FM and some were just NFPA 13. I have never run into any AHJ wanting ESFR heads under the catwalks or conveyors. They are normally treated as a separate system like a mezzanine would be, they have their own riser off of the manifold and all.

Reply
Jack G
12/8/2025 01:08:31 pm

I believe the separate calculations is because the roof ESFR s water is obstructed by the conveyors so a new calculation is required using the area under the conveyors as a new ceiling.

D
12/8/2025 08:52:10 am

Well, I learned something today. I would have thought, with the number of conveyors I have seen with standard spray sprinklers underneath them, that surely this plan reviewer was wrong. But it appears as though Brett guidance is correct. Seems the best bet is to attempt to cite 2025 edition which has specific language for conveyors.

Reply
Dan Wilder
12/8/2025 08:58:25 am

Agree with Brett and it is unfortunate that the previous design did not get flagged (not sure what the previous NFPA standard was) Having completed several DC's and this issue comes up a lot, we have provided ESFR beneath conveyors, including sloped installations, that match the overhead for sprinkler type, K-Factor, and pipe sizing and have had very little issue with inspections and Insurance sign offs. We have been able to use the lesser available storage height to use a less demanding ESFR sprinkler beneath larger catwalks and platforms.

Reply
Chad
12/8/2025 08:59:39 am

Yeah he is right. The slope under the conveyer is irrelevant when providing coverage under obstructions with ESFR when applying pre-2025 NFPA 13.

Gotta be ESFR below as well.

Reply
OP
12/8/2025 10:59:19 am

This is going to get interesting and will present a whole world of problems because of the existing heads being standard 5.6k spray heads. Thankfully the FP Installer used another design firm for the original conveyor layout so we're not reliable for it, but technically we should be replacing all the existing heads with ESFR or else we will have 1/2 a 5.6k standard and 1/2 k22 esfr. I guess we always got away with it because we would connect to the mezzanine systems which were standard heads because there is no storage below them. this particular building was built as a shell type warehouse with 42' ceilings, so I guess they used k22 esfr just to allow for almost any tenant to use the space.

Reply
OP
12/8/2025 11:07:27 am

Thank you all for your insight into this, I greatly appreciate it. Hopefully this will not be much of a huge deal for us, although I suspect it will be for my client.

Reply
Jack G
12/8/2025 01:03:05 pm

From what I recall the sprinklers under the conveyor are a separate calculation and treated as a new ceiling ( you do not need to add to the roof demand or calculate with roof sprinklers)

Reply
OP
12/8/2025 01:50:48 pm

That was my thought as well, however there isn't anything in NFPA 13 prior to 2025 that supports that. They are still run as a separate system, and calculated as one.

Reply
Anthony
12/8/2025 02:14:29 pm

This is a rough one, obstruction coverage needs to match the system above typically.

I could see an argument where the floor space covered is actually OH2 and considered manufacturing or finished goods processing and an F-1 or F-2. In those cases where ESFR is protecting a lower hazard I could see the sprinkler change acceptable.

Reply
JG
12/29/2025 04:35:17 pm

Just to clarify, the allowance to use standard spray sprinklers underneath conveyors was introduced in the 2022 edition of NFPA 13, when the whole conveyor section was added to chapter 14. Section 14.2.11.4 option (1) "Quick-response standard spray sprinklers shall be permitted to be installed below conveyors without high-piled storage located underneath". This is also the section that allows you to omit protection underneath conveyors up to 4'-0 wide.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top June '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT