I have a storage rack configuration that has been installed with a storage height of 20 ft and a ceiling height of 30 ft. The commodity is Group A expanded plastics in cartons. It is cardboard boxes with cushions and foams, and some are wrapped in cling wrap.
I am trying to determine whether in-rack sprinklers are required for this configuration. I have been reviewing the CMDA, CMSA, and ESFR sprinkler protection options. It is currently installed in a system that is designed in OH2. However, I think this is not sufficient. I believe there may be an opportunity to modify the system and use ceiling-only ESFR protection based on NFPA 13, Section 23.6.3, which specifies a demanding area of 12 sprinklers, consisting of four sprinklers on each of three branch lines. Based on Table 23.6.1, which addresses cartoned expanded plastics with a maximum storage height of 20 ft and a ceiling height of 30 ft- based on selecting an ESFR sprinkler K-factor and its corresponding minimum operating pressure, then calculate the required water demand for the 12 sprinklers? I would appreciate any clarification on whether I am interpreting these provisions correctly and whether this approach would be sufficient or if in-rack sprinklers are necessary. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Pete H
11/3/2026 06:30:17 am
You're reading it correctly, a 12 head esfr calc of either K14 or K16.8 esfr sprinklers (doing 50 or 35 psi per head as a minimum operating pressure respectively) is sufficient to void in-rack protection requirements as per the protection layout outlined in Table 23.6.1 (NFPA 13 2019 ed.) for a 30'-0" max ceiling height and 20'-0" max storage of cartoned expanded Group A plastics.
Reply
Jesse
11/3/2026 08:10:21 am
ESFR is intended for just this situation. Larger orifice ESFR sprinklers are easier to calculate due to the lower operating pressure. I've had several projects with non-expanded Group A where I was able to avoid a pump because I had a pretty robust water supply.
Reply
Mark Harris
11/3/2026 08:29:57 am
Agree with Jesse and Pete. You will probably need a fire pump and hopefully your existing underground supply is not 6". If it is you will probably need new larger.
Reply
Glenn Berger
11/3/2026 08:55:10 am
You have gotten some great advice. BTW, I hate working on storage facilities.
Reply
Streeter
11/3/2026 09:32:29 am
I do quite a few ESFR systems and have learned quite a few lessons from them along the way. Pay special attention to the orientation requirements for upright vs pendent as that is sometimes an issue when maintaining 18" deflector height from deck.
Reply
Dave
11/3/2026 03:28:28 pm
And if applicable (or employable), the changes in the 2025 edition NFPA 13 for ESFR, like sloped ceilings, obstructions, documentation.
Reply
danefre
11/3/2026 12:51:58 pm
Great advice above.
Reply
Michael
11/3/2026 01:23:53 pm
Follow up question since I have not seen any of the replies commenting on whether OP's storage arrangement in question is on solid shelf racks or open racks: wouldn't OP need to confirm if the storage is an open-rack configuration per NFPA 13 (2025) 23.1.3 before determining that no in-rack sprinklers are required?
Reply
Nimal Tissa,wijetunga
11/3/2026 09:07:24 pm
Your commodity classification is Group A plastic expanded /non exposed as per NFPA 13.
Reply
Bjørn
11/4/2026 07:27:01 am
ESFR - don't forget the flue spaces !!