MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Use Armored Cable for Controller to Pump?

7/31/2025

5 Comments

 
Is it permitted to install fire pump cables, from the controller panel to the motor, through a cable tray using armored cables, at a height of about 4 inches (10 cm) above the finished floor level?

Are there any code or standard requirements that affect this?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Sean
7/31/2025 08:16:51 am

This sounds like an NEC (NFPA 70) Article 230 and Article 695 reference exploration, as I believe there are various factors.

Reply
Todd Wyatt
7/31/2025 08:29:42 am

The scoping Code (e.g. IBC-2024) references NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection as it pertains to Fire Pumps. NFPA 20 references NFPA 70 NATIONAL ELECTRICAL CODE Article 695 Fire Pumps. See REFERENCES below.

From NFPA 70 NATIONAL ELECTRICAL CODE Article 695 Fire Pumps :
The requirements covering reliable power supplies for electric fire pump motors correlate with those in NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection.
However, the NEC and NFPA 20 have a distinct division of responsibility for fire pump requirements.
PERFORMANCE ISSUES, INCLUDING THE DETERMINATION OF POWER SUPPLY RELIABILITY, are under the jurisdiction of the NFPA TECHNICAL COMMITTEE ON FIRE PUMPS, while ELECTRICAL INSTALLATION REQUIREMENTS are within the purview of the NATIONAL ELECTRICAL CODE COMMITTEE.

Reply
Todd Wyatt
7/31/2025 08:30:14 am

REFERENCES

NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection
Chapter 10 Electric-Drive Controllers and Accessories
Enhanced Content
Chapter 10 describes the attributes of ELECTRIC MOTOR–DRIVEN FIRE PUMP CONTROLLERS, including CONTROLLERS WITH POWER TRANSFER SWITCHES AND SEPARATE POWER TRANSFER SWITCHES, all for use in electric fire pump motor circuits. Also covered in this chapter are accessories used with the controllers to ensure the minimum performance required by NFPA 20. The focus of Chapter 10 is the design, construction, and performance of the CONTROLLERS, transfer switches, and their accessories. This chapter also provides information to aid in SPECIFYING, INSTALLING, AND OPERATING THIS EQUIPMENT

10.1 General.
10.1.3* Design.
All ELECTRICAL CONTROL EQUIPMENT DESIGN shall comply with ARTICLE 695 OF NFPA 70 and other applicable documents.
A.10.1.3  
All electrical control equipment design should also follow the guidelines within NEMA ICS 14, Application Guide for Electric Fire Pump Controllers.
Enhanced Content
The role of NEC Article 695 is emphasized in 10.1.3. NFPA 20 covers the minimum performance and testing requirements for controllers and transfer switches, while Article 695 covers the installation requirements of such equipment. Some of the requirements of Article 695 are extracted from NFPA 20 because those requirements are under the purview of the NFPA 20 Technical Committee on Fire Pumps. However, all the installation requirements for controllers, transfer switches, and fire pump accessory equipment are in Article 695.


NFPA 70 NATIONAL ELECTRICAL CODE
Article 695 Fire Pumps
695.1 Scope.
(A) Covered.
This article covers the installation of the following:
(1) Electric power sources and interconnecting circuits
(2) Switching and control equipment dedicated to fire pump drivers
Informational Note: Text that is followed by a reference in brackets has been extracted from NFPA 20-2019, Standard for the Installation of Stationary Pumps for Fire Protection. Only editorial changes were made to the extracted text to make it consistent with this Code.
(B) Not Covered.
This article does not cover the following:
(1) The performance, maintenance, and acceptance testing of the fire pump system and the internal wiring of the components of the system
(2) The installation of pressure maintenance (jockey or makeup) pumps
Informational Note No. 1: See Article 430 for the installation of pressure maintenance (jockey or makeup) pumps supplied by the fire pump circuit or another source.
(3) Transfer equipment upstream of the fire pump transfer switch(es)
Informational Note No. 2: See NFPA 20-2019, Standard for the Installation of Stationary Pumps for Fire Protection, for further information.
(4) Water pumps installed in one- and two-family dwellings and used for fire suppression
Informational Note No. 3: See NFPA 13D-2019, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, for further information.

Enhanced Content
The requirements covering reliable power supplies for electric fire pump motors correlate with those in NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection. However, the NEC and NFPA 20 have a distinct division of responsibility for fire pump requirements. PERFORMANCE ISSUES, INCLUDING THE DETERMINATION OF POWER SUPPLY RELIABILITY, are under the jurisdiction of the NFPA TECHNICAL COMMITTEE ON FIRE PUMPS, while ELECTRICAL INSTALLATION REQUIREMENTS are within the purview of the NATIONAL ELECTRICAL CODE COMMITTEE.

ELECTRIC MOTOR–DRIVEN FIRE PUMPS are covered by the requirements of ARTICLE 695. If a pump is installed in accordance with NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, the requirements of Article 695 and NFPA 20 do not apply to the electrical installation.

Although the installation requirements for pressure maintenance (jockey) pumps are not covered by Article 695, these pumps are permitted by NFPA 20 to be supplied by a fire pump service or feeder or by a separate supply.

In respect to the power supply for a fire pump, Article 695 permits a single source if it is deemed to be reliable by the AHJ. This differs from the approach taken in Article 700 for emergency systems, where in

Reply
Todd Wyatt
7/31/2025 08:30:45 am

REFERENCES

NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection
Chapter 10 Electric-Drive Controllers and Accessories
Enhanced Content
Chapter 10 describes the attributes of ELECTRIC MOTOR–DRIVEN FIRE PUMP CONTROLLERS, including CONTROLLERS WITH POWER TRANSFER SWITCHES AND SEPARATE POWER TRANSFER SWITCHES, all for use in electric fire pump motor circuits. Also covered in this chapter are accessories used with the controllers to ensure the minimum performance required by NFPA 20. The focus of Chapter 10 is the design, construction, and performance of the CONTROLLERS, transfer switches, and their accessories. This chapter also provides information to aid in SPECIFYING, INSTALLING, AND OPERATING THIS EQUIPMENT

10.1 General.
10.1.3* Design.
All ELECTRICAL CONTROL EQUIPMENT DESIGN shall comply with ARTICLE 695 OF NFPA 70 and other applicable documents.
A.10.1.3  
All electrical control equipment design should also follow the guidelines within NEMA ICS 14, Application Guide for Electric Fire Pump Controllers.
Enhanced Content
The role of NEC Article 695 is emphasized in 10.1.3. NFPA 20 covers the minimum performance and testing requirements for controllers and transfer switches, while Article 695 covers the installation requirements of such equipment. Some of the requirements of Article 695 are extracted from NFPA 20 because those requirements are under the purview of the NFPA 20 Technical Committee on Fire Pumps. However, all the installation requirements for controllers, transfer switches, and fire pump accessory equipment are in Article 695.


NFPA 70 NATIONAL ELECTRICAL CODE
Article 695 Fire Pumps
695.1 Scope.
(A) Covered.
This article covers the installation of the following:
(1) Electric power sources and interconnecting circuits
(2) Switching and control equipment dedicated to fire pump drivers
Informational Note: Text that is followed by a reference in brackets has been extracted from NFPA 20-2019, Standard for the Installation of Stationary Pumps for Fire Protection. Only editorial changes were made to the extracted text to make it consistent with this Code.
(B) Not Covered.
This article does not cover the following:
(1) The performance, maintenance, and acceptance testing of the fire pump system and the internal wiring of the components of the system
(2) The installation of pressure maintenance (jockey or makeup) pumps
Informational Note No. 1: See Article 430 for the installation of pressure maintenance (jockey or makeup) pumps supplied by the fire pump circuit or another source.
(3) Transfer equipment upstream of the fire pump transfer switch(es)
Informational Note No. 2: See NFPA 20-2019, Standard for the Installation of Stationary Pumps for Fire Protection, for further information.
(4) Water pumps installed in one- and two-family dwellings and used for fire suppression
Informational Note No. 3: See NFPA 13D-2019, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, for further information.

Enhanced Content
The requirements covering reliable power supplies for electric fire pump motors correlate with those in NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection. However, the NEC and NFPA 20 have a distinct division of responsibility for fire pump requirements. PERFORMANCE ISSUES, INCLUDING THE DETERMINATION OF POWER SUPPLY RELIABILITY, are under the jurisdiction of the NFPA TECHNICAL COMMITTEE ON FIRE PUMPS, while ELECTRICAL INSTALLATION REQUIREMENTS are within the purview of the NATIONAL ELECTRICAL CODE COMMITTEE.

ELECTRIC MOTOR–DRIVEN FIRE PUMPS are covered by the requirements of ARTICLE 695. If a pump is installed in accordance with NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, the requirements of Article 695 and NFPA 20 do not apply to the electrical installation.

Although the installation requirements for pressure maintenance (jockey) pumps are not covered by Article 695, these pumps are permitted by NFPA 20 to be supplied by a fire pump service or feeder or by a separate supply.

In respect to the power supply for a fire pump, Article 695 permits a single source if it is deemed to be reliable by the AHJ. This differs from the approach taken in Article 700 for emergency systems, where in

Reply
chad
7/31/2025 08:36:29 am

As an AHJ I would not accept any method not prescribed in 695.6.(D) (1)

695.6 Power Wiring (D) Pump Wiring (1) Wiring Methods.

Wiring from the controller(s) to the pump motor shall be in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit LFNC-B, listed Type MC cable with an impervious covering, or Type MI cable



When you say armored cable, if you mean one of the above methods and you want to put it in cable tray, as long as its not subject to damage in the tray, that should be ok but that can be hard to accomplish in a busy pump room

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT