MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Use 2-Hour Gyp. Chase for Standpipe Protection?

3/28/2025

11 Comments

 
Section 9.2.2 in NFPA 14 allows protection for a standpipe that is not in a stairway to be "the piping is enclosed in fire-rated construction with a rating equal to that of the enclosed fire-rated exit stairway."

In the Gypsum Association Manual WP 3910 for a chase wall with staggered studs has a rating of 2 hours.

Does such a 2-hour rated chase meet the intent of NFPA 14 when the standpipe is not in the stair?

Thank you for your feedback!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
11 Comments
Dan Wilder
3/28/2025 07:51:25 am

Possibly....for some projects we have dealt with in the past

If the standpipe resides between two of these wall assemblies, then yes it complies assuming the top and bottom wall caps and floor/ceiling-roof deck meets the same rating for the construction.

If the intent is to run the standpipe within the wall then no as the rating is based on a symmetrical rating utilizing both sides of the wall.

A better option would look closer to a rated shaft wall or soffit with an asymmetrical rated wall construction (all the gyp board on one side) as this allows construction without access to one side of the wall/soffit system and maintains rating.

Look at UL Design V497 for examples or WP7125 looks similar to what I have seen in the past.

Reply
Paul Pinigis link
3/28/2025 08:15:00 am

You can build an enclosure with this wall construction, but you cannot install the pipe within the wall because that would not provide the required 2-hour protection. The 2-hour rating of this wall is from one side of the wall to the other, not from one side of the wall to the interior of the wall.

Additionally This wall would either have to be free-standing from the slab-on-grade or would have to be supported by 2-hour floors that are supported on 2-hour structure.

Reply
Glenn Berger
3/28/2025 08:18:08 am

A 2-hour fire-rated chase can be constructed to meet the requirements in NFPA 14. Additional detailing will need to be completed to achieve compliance with the reference provided.

Reply
Adam
3/28/2025 08:42:43 am

In Ontario, fire-rated walls are based on the fire resistance of one side to the interior, but they need to be constructed with an equal rating on either side.

Once the fire has penetrated the membrane of the wall, the structure is then in direct contact with the fire. The gypsum on the opposite side of the wall does not have support once the studs have burned away.

The two layers of Type-X give you a 2-hour rating on the side that it is installed, but having two layers on each side does not achieve a 4-hour rating because the structure starts to burn once the exposed side is compromised.

I would say that installing the pipe within the wall is acceptable.

Reply
Paul Pinigis link
3/28/2025 08:47:32 am

I am not aware of any calculation that equates two layers of Type X gypsum board to a 2-hour fire-resistance rating. The listed endurance for 5/8" Type X gypsum board is 40 minutes, so 2 layers provides 80 minutes of protection. You could use thicker gypsum board, but the detail provided utilized 5/8"

Reply
Adam
3/28/2025 08:58:59 am

The Ontario Building Code describes the "component additive method" which takes into account the framing and any insulaton as well. This can bring you up to 115 minutes with insulation - just shy of 2-hours. In addition to this calculation, the OBC provides approved fire- and sound-rated assemblies in their supporting documentation. Many of these assemblies, rated for two hours include two layers of type-X. It's also not uncommon to find UL-listings that allow this (similar to the example in the OP). So while a calculation method might not bring you to two-hours, the right listing or documentation will allow it.

Jack G
3/28/2025 10:27:57 am

It is my understanding that in fully sprinklered buildings a 1 hr enclosure is required, 4 or greater 2 hour.
So any rated enclosure appropriate for the standpipe can be used.
The enclosure is also included for laterals ( to hose valves, laterals of class 1 standpipes shall be protected with a degree of fire protection equal to that of an exit stair, exception being fully sprinklered buildings. Here’s the sticky part. IBC definition of laterals is from the 2013 edition of NFPA 14, which , by the IBC will require lateral and supply enclosure of the piping if not enclosed in the exit stair.
Later editions ( NFPA 14) do not require the enclosure for laterals/ supplies for standpipes, but the IBC definition is stuck with the 2013 definition.
Horizontal standpipes ( single story) are another animal and can be fire wrapped.

Reply
Jesse
3/28/2025 11:21:38 am

The short answer is "yes".

The longer answer is that the GC needs to ensure the standpipe main is in a chase that really is 2-hr rated. We had a project we designed like this in a hotel renovation where the GC provided 1-hr rating on both sides of the chase - and 1hr + 1hr = 2hr right??

Reply
Jeff Ayers
3/28/2025 11:57:51 am

The short answer is ACTUALLY NO. Because 2-hour shaft enclosures are typically only required for multiple stories and the wall type shown is for 1 level.

Why? Because the standpipe for the FHV is penetrating more than one floor ceiling assembly. The wall detail you show is designed to be installed from slab to ceiling, not continue up multiple levels.

The 2-hour shaft will be installed UNINTERRUPTED from the second floor up through all subsequent floors. (Most shaft walls can stack up to 45' and 1 UL assembly allows up to 65' vertical stacking.

In IIIA (5 level) and podium projects up to 2 levels (2 levels max to avoid being classified as a high-rise at 75' from apparatus access) the shaft will start on top of the podium and extend through the top level. The shaft wall is typically UL U428 and it sits in front of the corridor demising wall, allowing an opening in the floor at each level for the shaft wall to stack.

Note that some AHJ's want the horizonal runs from the standpipe in the stairwells to be 2- hour- running laterally to the vertical standpipe. Others allow the horizontal to be run in the truss spaces which is a 1-hour floor ceiling assembly.

The wall assembly you show would only work at 1-story assemblies. In that case the lateral being fed through the ceilings will turn down into the 2-hour wall you have shown.

Reply
Todd E Wyatt
3/31/2025 10:06:33 am

The fire-resistance rating (FRR) of an Interior Exit Stairway (IES) should be determined by the Design Professional (e.g. Architect). The FRR of the IES is determined by both the number of stories it connects (1-Hour <4 stories or 2-Hours >4 stories) and the FRR of the Floor Assembly it penetrates :

IBC-2024
Chapter 10 Means of Egress
Section 1023 Interior Exit Stairways and Ramps
1023.2 Construction
Enclosures for interior exit stairways and ramps shall be constructed as fire barriers in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Interior exit stairway and ramp enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the interior exit stairways or ramps shall include any basements, but not any mezzanines. Enclosures for interior exit stairways and ramps shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours.

The "Protection of Piping from Fire Damage" has (4) methods listed ...

NFPA 14-2024
9.2.2 Protection of Piping from Fire Damage.
Class I and Class III standpipe system aboveground piping shall be protected from fire damage by one of the following methods:
1. The piping is enclosed in a fire-rated exit stairway.
2. The piping is enclosed in fire-rated construction with a rating equal to that of the enclosed fire-rated exit stairway.
3. Listed fire wrap or other insulating material is applied directly to the pipe with a rating equal to that of the enclosed fire-rated exit stairway.
4. Other methods acceptable to the AHJ.

... but IF the building is already protected by an automatic sprinkler system (ASPS), then "horizontal standpipes" not located in a FRR stair enclosure are req'd to be protected :

9.2.2.4*
Where buildings are fully sprinklered in accordance with NFPA 13 or NFPA 13R, feed mains, express mains, express risers, HORIZONTAL STANDPIPES, and branch lines that are not located in rated stair enclosures shall not be required to be protected from fire damage.

Here are other exceptions for NOT protecting standpipes from fire damage :

9.2.2.1
Where exit stairways are not required to be enclosed in fire-rated construction, standpipe systems shall not be required to be protected from fire damage.
9.2.2.2
Class II standpipe system piping shall not be required to be protected from fire damage.
9.2.2.3
Where additional standpipes are provided outside of stair enclosures to meet travel distance requirements in non-high-rise buildings, protection of additional standpipes from fire damage shall not be required.

Reply
Todd E Wyatt
4/3/2025 01:40:27 am

CORRECTION ...

... but IF the building is already protected by an automatic sprinkler system (ASPS), then "horizontal standpipes" not located in a FRR stair enclosure are NOT req'd to be protected ...

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT