|
Good morning, I am in Florida and use the Florida Fire Prevention Code 8th Edition, which references NFPA 1 and 101 (2021), NFPA 72 (2019), NFPA 96 (2021), and NFPA 17A (2021).
I have a mixed occupancy strip mall that is fully sprinklered and has a fire alarm that was initially installed to monitor the sprinklers only. One tenant upgraded the panel to accommodate a full fire alarm for their unit. A different tenant, mercantile class C, in the strip mall has installed a hood and hood suppression system along with duct detectors for their upgraded AC system. The ducts serve only their unit and do not cross demising walls or serve other units. My interpretation is that the duct detectors and hood suppression systems must be tied into the building's fire alarm. Is this correct? Another question, would this tenant then need to upgrade their unit to include pulls and notification appliances? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments
Chad
10/27/2025 07:25:52 am
The hood system has to be monitored by the fire alarm.
Reply
Glenn Berger
10/27/2025 09:28:19 am
Total agreement with Chad. I was involved with the duct detector issue with USACE last week for a project in Alaska.
Reply
Ricardo Gonzales
10/27/2025 11:04:35 am
I disagree with the above gentlemen. 1st. The building has a sprinkler monitoring system is it not a Fire Alarm System.
Reply
Robert Morgan
10/27/2025 01:05:46 pm
I agree with Mr. Gonzales here,
Reply
Chad
10/27/2025 01:54:03 pm
From the OP" One tenant upgraded the panel to accommodate a full fire alarm for their unit."
Reply
Jim (OP)
10/29/2025 10:18:38 am
Thank you all for the insight and a lot to chew on. I appreciate all of the expertise! This is a great forum.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Dec '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
February 2026
PE PREP SERIES |
RSS Feed
