MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Swap Heat for Smoke in Nonsprinklered Building?

8/13/2024

11 Comments

 
Hi, I am a Fire Alarm system installer and have been active for 25 years.

I am writing today because the change from the UBC to the IBC, or some other change that I am unaware of, has removed the requirements to do anything in an existing un sprinklered building in Washington state.

Looking at the requirements for E occupancy, specifically for a sprinklered building, it says to install heat detectors in most locations. There is no guidance for what to do in an existing non-sprinklered building. This has led some to remove smoke detectors from projects and install only heat detectors other than the one for the panel and power supplies, treating sprinklered buildings and non-sprinklered buildings the same.

I am alarmed by this and think it’s a mistake we will regret. On a sprinklered building, you have suppression, so the fire will likely be in a controllable state when first responders arrive. It makes sense that early warning would be redundant, other than areas like exit pathways or sleeping areas where someone could be overcome with smoke or the exit path may be blocked. Early warning devices are necessary in those cases. If we get the people out safely, then the firemen don’t need to go in. Early warning devices achieve that.

But on a non-sprinklered building there is no suppression. Heat detectors do not go into alarm until the fire reaches them, they are mounted on the ceiling so the walls and building will be on fire before they activate. Smoke detectors will go off when the fire is smoldering getting the first responders on the way before the building is on fire. Oh, and getting the people out of the building before it’s on fire, one of my personal favorites.

My goals, 1. I wanted to add some beam smoke detectors over the gym floor area and some smoke detectors over the stage due to the large amounts of fabric. 2. I intended on replacing all the devices on the permitted installation with like for like. Resulting in smoke detectors in the areas that currently have smoke detectors.

Both of my submittals (to the architect) showing smoke detectors were rejected and I was instructed to show heat detectors. I have no way to argue for the smoke detectors, there is no guidance I can find. We are removing all the life safety out of the life safety systems.

Is there something I am missing, is there a way I can fight to get smoke detection in the halls and classrooms that do not have an exit doors?

I looked at the 2021 IFC chapter 11, specifically 1103. I hoped I had found my solution but reading it more carefully, I see the intent of that statement is the table. I can’t find anything on that table that will keep the early warming detection in the life safety system. I know the goal is to reduce false alarms. Smoke detectors have a bad reputation for unwanted alarms. On this project they were suffering from false alarms. That is the reason they are wanting to eliminate smoke detectors. With in a half hour of being on site the existing system went into alarm. I viewed the point, found out it was a 135 fixed temp heat installed in an attic that was at 150. So Heat detectors false alarm as well when incorrectly applied to the environment or poorly maintained.

​Are we going to regret this or am i just an old man with old ways of doing things?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments
RayJ link
8/13/2024 08:19:32 am

If I were in this situation, I would ask the architect if he would be comfortable with his children and grandchildren, if any, going to classes in this type of environment. Sometimes, some people have to be shown, or told to be able to see the entire picture. I would always err to the side of caution and take the extra steps, no matter. Sadly, a lot of people only care about money, and can't see the forest because the trees are in the way.

Reply
OP
8/13/2024 03:54:55 pm

Ray,
Yea its all about the perceived cost. Heats are less expensive.
I am not sure they will feel the same after the wrongful death lawsuits.
The few dollars more for a smoke will protect you from explaining why you went with a devices that says "not a life safety devices" on the side.
This is really a dangerous time for us.
Thank you for your reply.

Reply
Ed Glynn link
8/13/2024 08:46:14 am

You are 100% correct. All one has to do is look at the listings on heat detectors and see that heat detectors are not listed as Life Safety devices.

They have their place in mechanical rooms and elevator machine rooms but not in non-sprinkled buildings were smoke detectors should be installed.

Reply
Jon N
8/13/2024 09:15:11 am

As it appears that you have already surmised, heat detection has virtually no life safety benefit. By the time they activate, the temperatures are very high and, more importantly, the amount of smoke being generated is life-threatening (from both inhalation and visual impairment perspectives).

This was in a former policy that we had when I was an AHJ. It was a hierarchy of fire protection strategies. You could always substitute upward for protection but never downward:
1. Fire sprinkler systems - active system that suppresses fire and provides notification of occupants and fire department
2. Other automatic extinguishing systems - active system that suppresses fire but often has limited agent
3. Fire alarm systems with smoke detection - active system that provides early warning and life safety benefit (especially where people sleep). No suppression value
4. Compartmentation - passive protection that limits the spread of fire. Does not suppress fire or notify the occupants
5. Fire alarm systems with heat detection - active system but activates too late to be of any life safety benefit. No suppression value
6. Smoke control systems - active system integrated with smoke detection; may provide some additional egress time. No suppression value
7. Standpipe systems - passive system typically for fire department use. FD must be notified and present. Some suppression value but not automatic
8. Staff training and response - passive response relying on human action. Some history of success in institutional occupancies but little to no value in other occupancies.

Reply
Todd E Wyatt
8/13/2024 10:07:57 am

The currently adopted Existing Building Code for the State of WA is “2021 Washington State Existing Building Code” (https://codes.iccsafe.org/content/WAEBC2021P1)

The requirements for Fire Alarms in an “alteration” of an existing building is based on the “Level of Alteration” (1, 2, or 3).

Alterations - Level 1 : (0) references to “Fire Alarm”
Alterations - Level 2 : (16) references to “Fire Alarm” (803.4.1)
Alterations - Level 3 : (5) references to “Fire Alarm” (904.2 … see IBC Section 907 as req’d for New Construction).

Once the Alteration Level is determined (see WSEBC-2021 Chapter 6), review the requirements for Fire Alarms. For Alterations - Level 2, 803.4.1.1 Group E states “A fire alarm system shall be installed in work areas of Group E occupancies as required by the International Fire Code for existing Group E occupancies.”

Reply
Todd E Wyatt
8/13/2024 10:08:14 am

REFERENCES

WSEBC-2021
Chapter 8 Alterations—Level 2
Section 803 Fire Protection
803.4 Fire Alarm and Detection
An approved fire alarm system shall be installed in accordance with Sections 803.4.1 through 803.4.2. Where automatic sprinkler protection is provided in accordance with Section 803.2 and is connected to the building fire alarm system, automatic heat detection shall not be required.
An approved automatic fire detection system shall be installed in accordance with the provisions of this code and NFPA 72. Devices, combinations of devices, appliances, and equipment shall be approved. The automatic fire detectors shall be smoke detectors, except that an approved alternative type of detector shall be installed in spaces such as boiler rooms, where products of combustion are present during normal operation in sufficient quantity to actuate a smoke detector.

803.4.1 Occupancy Requirements
A fire alarm system shall be installed in accordance with Sections 803.4.1.1 through 803.4.1.6. Existing alarm-notification appliances shall be automatically activated throughout the building. Where the building is not equipped with a fire alarm system, alarm-notification appliances within the work area shall be provided and automatically activated.
Exceptions:
Occupancies with an existing, previously approved fire alarm system.
Where selective notification is permitted, alarm-notification appliances shall be automatically activated in the areas selected.

803.4.1.1 Group E
A fire alarm system shall be installed in work areas of Group E occupancies as required by the International Fire Code for existing Group E occupancies.

803.4.1.2 Group I-1
803.4.1.3 Group I-2
803.4.1.4 Group I-3
803.4.1.5 Group R-1
803.4.1.6 Group R-2

803.4.2 Supplemental Fire Alarm System Requirements
Where the work area on any floor exceeds 50 percent of that floor area, Section 803.4.1 shall apply throughout the floor.
Exception: Alarm-initiating and notification appliances shall not be required to be installed in tenant spaces outside of the work area.

Chapter 9 Alterations—Level 3
904.2 Fire Alarm and Detection Systems
Fire alarm and detection shall be provided in accordance with Section 907 of the International Building Code as required for new construction.
904.2.1 Manual Fire Alarm Systems
Where required by the International Building Code, a manual fire alarm system shall be provided throughout the work area. Alarm notification appliances shall be provided on such floors and shall be automatically activated as required by the International Building Code.
Exceptions:
1. Alarm-initiating and notification appliances shall not be required to be installed in tenant spaces outside of the work area.
2. Visual alarm notification appliances are not required, except where an existing alarm system is upgraded or replaced or where a new fire alarm system is installed.
904.2.2 Automatic Fire Detection
Where required by the International Building Code for new buildings, automatic fire detection systems shall be provided throughout the work area.

Chapter 2 Definitions
WORK AREA.
That portion or portions of a building consisting of all reconfigured spaces as indicated on the construction documents. Work area excludes other portions of the building where incidental work entailed by the intended work must be performed and portions of the building where work not initially intended by the owner is specifically required by this code.

Reply
Jack G
8/13/2024 12:22:27 pm

I think the forum has hit it.
You should present the Fire Marshal with the results listed above. Jon indicates there might be a guideline within municipalities that outline the preference and use of detection devices. Heat detectors are not listed as life safety devices as indicated by Ed above.
Send the same letter to the architect/ engineer.
Stir the pot. I m sure the AHJ will not want heat detectors, putting it back in the engineers court, to provide something else.
At the same time, work up a proposal for a new automatic sprinkler
If they are interested in life safety, you ll have gotten yourself a bigger contract. It’s worth the time if only to provide a ballpark for next years budget.
This has worked for me many times over the last 55 years.
Schools are required to upgrade and to have sprinkler systems ( in 2 of the 3 states I work in , over the last 10 years )

Reply
op
8/13/2024 04:46:41 pm

Jack,
Sorry i did not included you in the group reply.
Thank you.
I have stirred the pot. I could not stand by and let this happen. Had to go over everyone's head to the FM, make the case and let him overrule everyone.
Feels like kindergarten tattling though, I want a more professional way of addressing it.
I am going to use those codes to fight it directly next time.

Reply
OP
8/13/2024 04:35:39 pm

I was going to reply to each of you individually, you took the time to reply so i owe you that much, however it may spam people with a bunch of replays instead of one. So I am going to replay to all here.

Ray, thanks again. got you up above.

ED, I know! Right! This is insane!

John, Thank you. Some of that i had already adopted into my risk assessment, but your list includes "other automatic extinguishing system" that I had never factored in. I am going to adopt yours.

Todd, The amount of work you put into that reply is exceptional Thank you. Where i am going wrong, is i start with the IBC even in an existing building, and I see that I should be starting in the WSEBC for existing buildings. .

I had already took action on this. Due to the existing approval on the system i decided the best thing to do was reach out to the FM for his direction.
Before contacting him I did a risk assessment of the property.
I found egress code deficiencies. Over occupancy and un rated corridors that sort of thing.
Due to that information and the fact that smoke detection was the previous approved protection for those areas, the FM suggested he would only approve smoke detections.

That is what i submitted. We await his decision.

In the future ill use the code Todd laid out and be able to defend smoke detection from the start.

Thank you all.

Reply
DPC
8/13/2024 06:45:15 pm

All "E" occupancies are required to be Fire Sprinkled.
If it is existing you have to add fore sprinklers.

As mentioned earlier my child my grandchild...

Reply
op
8/14/2024 07:40:48 pm

Yea, but they are not going to.

They are trying to use the lack of instruction on what to do when a sprinkler system is not going to be installed to remove smoke detectors from the paths of egress, on an existing approved system.

So we will not have suppression from the sprinkler system and if I did not fight this we would of not have had early warning either.

I feel the FM will decided on smoke detection for those areas.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Feb '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT