|
I'm working on a fire protection design for a new apartment building. The architect is adding what they're calling horizontal exits throughout the building, which will increase the number of required standpipes per the local building code (IBC-based, 2025) Section 905.4.
Per the exception to 905.4.2, I do not believe we will need hose connections on both sides of every horizontal exit within the building. I think additional standpipes and hose connections will only be required in the center of the building. Other than the egress stairwells, where are standpipes and hose connections required to be located? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Dan Wilder
4/8/2026 07:58:15 am
Looking at the exception for this section, no additional hose valves (or suppling standpipes) would be needed for any of the doors within 100' of the exit stairwells.
Reply
Glenn Berger
4/8/2026 08:15:00 am
There is a problem with the horizontal exit concept. There is a provision that the maximum number of horizontal exits is 50% from any given spot (or similar language).
Reply
Jim Grostick
4/8/2026 08:22:58 am
Good points on the distance math. One thing worth flagging from an operational standpoint: firefighters are trained to follow their hose line back to safety when conditions deteriorate. If that line leads to a mid-corridor standpipe connection instead of a protected stairwell, they’re retreating to an unprotected space — which is a real problem in a fast-moving fire.
Reply
Laura L Henning
4/8/2026 08:57:55 am
That's a lot of horizontal cross corridors duel swings. First question is are they all horizontal egress walls, or are they IBC 706 fire walls for area separation, smoke barrier walls for smoke compartment or a rated fire barrier? Egress codes require at least 50% or more exits in a horizontal egress to exit to the outside or a stairwell opening directly to the outside. in theory only one set can be a horizontal exit, but the others could be fire walls or smoke barriers.
Reply
Todd Wyatt
4/8/2026 09:15:32 am
Horizontal Exits (HE) in this residential application are typically added to a story based on the Exit Access Travel Distance (EATD) to the (2) Exits … the (2) Interior Exit Stairways (IES) … exceeding the maximum 250-FT for R-2 that is protected by an automatic sprinkler system (ASPS) per the scoping Code (e.g. IBC-2024 TABLE 1017.2).
Reply
Todd
4/8/2026 09:26:29 am
IBC-2024 905.4 Location of Class I Standpipe Hose Connections (SHC) includes the prescriptive requirements for a SHC at a HE :
Reply
Todd Wyatt
4/10/2026 07:45:35 am
CORRECTION : The halfway point between the (2) Interior Exit Stairways (IRS) is approximately 108 FT (not 147 FT) which WOULD meet the 130 FT maximum (100 FT of hose + 30 FT of hose stream) so additional standpipe connections at a central HE location would NOT be required.
Jack G
4/10/2026 08:10:10 am
Rather than put a standpipe hose valve in the middle of a corridor in the center of the building, and none are required at the building doors, a good point made was the firemen following the hose,
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop April '26 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
April 2026
PE PREP SERIES |
RSS Feed
