I am being told that I need to install a standpipe on my warehouse roof because IBC 905.4 calls out the location of Class I standpipe hose connection in locations where the roof slope is 4 units vertical and 12 units horizontal.
However, my building is a single-story warehouse and doesn't meet the conditions established in section 905.3.1. Am I required to put in a standpipe because of Section 905.4? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Pete H
8/27/2026 06:16:42 am
Do you fall into any of the conditions in 905.3.2 through 905.3.8?
Reply
John
8/27/2026 10:52:33 am
Building is an S-1 warehouse... conditions for 905.3.2-905.3.8 don't apply.
Reply
Chris H
8/27/2026 08:15:11 am
Who is telling you that you need a standpipe system?
Reply
Ed Berkel
8/27/2026 08:19:58 am
A standpipe to the roof would NOT be required for a 1-story building. The reference to 1011.12 is why. 1011.2 only requires the access when the building is four stories or more and the slope is less than 4:12.
Reply
Dan Wilder
8/27/2026 08:30:26 am
Can you confirm you do not fall into any of the conditions in Chapter 32, like maybe 3206.9 when Exit Passageways are required?
Reply
John
8/27/2026 11:08:13 am
Request for standpipe is being based on roof pitch and servicing roof.
Reply
Jack G
8/27/2026 12:05:32 pm
905.3 only requires a standpipe system when specific conditions are met:
Reply
CASEY MILHORN
8/27/2026 12:32:23 pm
Agree with others. Not required at all. From a practical perspective, I can't imagine a fire fighter even getting on that roof for active fire fighting during a fire event... but I'm not a first responder, so.... if they are up there, it's because someone is trapped on the roof I hope?
Reply