Sprinklers Required with Combustible Insulation?

8/11/2026

9 Comments

 
Are sprinklers required in a noncombustible concealed space that contains combustible insulation?

I have a contractor who is trying to use polyurethane spray foam insulation in a noncombustible concealed space above a ceiling. It is an NFPA 13 system and they do not want to sprinkler it.

To my knowledge, this spray foam insulation is combustible, and by filling a noncombustible space with it, it will need sprinklers. They are trying to propose intumescent paint, but I don't believe that changes anything for them.

Do you all know of any applicable exceptions in this situation or if they don't need sprinklers?

I think 9.2.1.13 is the only relevant section from 13, but I am having trouble finding whether this foam exceeds the 1,000BTU per square foot. Thank you.

​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Jesse
8/11/2026 08:30:09 am

In order to omit AS protection in the atic, the void needs to be filled with non-combustible or limited combustible insulation. There are many spray foam insulation products that are cocmbustible, and that would negate the reasoning for omitting protection there.

Reply
anthony
8/11/2026 09:02:57 am

Jesse has it here. Add combustible construction to an otherwise non combustible space it becomes a combustible space. This isn't a trick question here.

Reply
OP
8/11/2026 10:54:20 am

This was my thinking. Just wanted to make sure I wasn't being ignorant because the customer does not agree with me and I like to check myself before putting my foot down.

Todd Wyatt
8/11/2026 08:34:11 am

The scoping Code (e.g. IBC-2024) requires WHERE an automatic sprinkler system (ASPS) is required to be installed per Occupancy Classifications, Specific Building Areas and Hazards, and/or during Construction.

The referenced Standard (e.g. NFPA 13-2025) includes omissions to ASPS installation.

If the Contractor is attempting to utilize the NFPA 13 9.2 Allowable Sprinkler Omission Locations of “filling an unsprinklered combustible concealed space with noncombustible insulation”, the insulation is required to be “noncombustible.”

Concealed spaces over isolated small compartments not exceeding 55 SF in area shall not require sprinkler protection.

Concealed spaces over horizontal chases and soffits not exceeding 160 CSF in volume shall not require sprinkler protection.

Reply
Todd Wyatt
8/11/2026 08:34:55 am

REFERENCES

IBC-2025
Chapter 9 Fire Protection and Life Safety Systems
Section 903 Automatic Sprinkler Systems
903.2 Where Required
903.2.1 Group A
903.2.2 Group B
903.2.3 Group E
903.2.4 Group F-1
903.2.5 Group H
903.2.6 Group I
903.2.7 Group M
903.2.8 Group R
903.2.9 Group S-1
903.2.10 Group S-2 Parking Garages
903.2.11 Specific Building Areas and Hazards
903.2.12 During Construction

NFPA 13-2025
Chapter 9 Sprinkler Location Requirements
9.2 Allowable Sprinkler Omission Locations.
9.2.1.7
Concealed spaces filled with NONCOMBUSTIBLE INSULATION shall not require sprinkler protection.
9.2.1.7.1
A maximum 2 in. (50 mm) air gap at the top of the space shall be permitted.
INSIGHTS : In some cases, filling an unsprinklered combustible concealed space with noncombustible insulation might be more economically advantageous than installing sprinklers. It is frequently a practical problem to completely fill concealed spaces with insulation. In the 2013 edition, language was added to permit a 2 in. (50 mm) air gap between the top of the insulation and the roof or ceiling above. Exhibit 9.4 provides an example of this requirement.
9.2.1.8
Concealed spaces within wood joist construction having noncombustible insulation filling the space from the ceiling up to the bottom edge of the joist of the roof or floor deck shall not require sprinkler protection.
9.2.1.9
Concealed spaces within composite wood joist construction having noncombustible insulation filling the space from the ceiling up to the bottom edge of the composite wood joist of the roof or floor deck and with the joist channels separated into volumes each not exceeding 160 ft3 (4.5 m3) to the full depth of the composite wood joist, with material equivalent to the web construction, shall not require sprinkler protection.
9.2.1.10
Concealed spaces over isolated small compartments not exceeding 55 ft2 (5.1 m2) in area shall not require sprinkler protection.
9.2.1.11*
Concealed spaces created by soffits of combustible construction below noncombustible or limited combustible ceilings separated into volumes each not exceeding 160 ft3 (4.5 m3) by noncombustible or limited combustible materials shall not require sprinkler protection.
A.9.2.1.11
Sprinklers are allowed to be omitted from horizontal chases and soffits that have noncombustible or limited combustible finishes that can contain mechanical and or plumbing equipment, ductwork, or electrical components. The 160 ft3 (4.5 m3) limitation is intended to limit the movement of fire within the chase or soffit. It is not the intent of this volume limitation to require dampers or other mechanical separations within ductwork, or other equipment that are not otherwise required.
INSIGHTS : The types of concealed spaces addressed by 9.2.1.11 and A.9.2.1.11 create spaces similar to other concealed space areas already addressed by the standard. This language makes it clear that these types of spaces, regardless of what mechanical and or plumbing equipment, ductwork, or electrical components are present in the space, are not required to be sprinklered provided they meet the conditions outlined in 9.2.1.11. The 160 ft³ (4.5 m³) limitation is consistent with other permissions for the omissions of sprinklers in concealed spaces throughout Section 9.2, such as those found in 9.2.1.6 and 9.2.1.9.

Reply
Erik
8/11/2026 09:07:43 am

9.2.1.1 NFPA 13 (2019) - Concealed spaces of noncombustible and limited combustible construction with MINIMAL combustible loading having no access shall not require sprinkler protection.

Seems to me, you have a lot more than minimal amount of combustible material up there and it would require sprinkler protection.

In regard to intumescent paint, I highly doubt there is a listing that would allow it to be used on combustible insulation. Typically intumescent paint is planned for because it has very specific listing / requirements, I don't know if I have ever seen it used as an after thought to make up for a missed mistake.

Reply
OP
8/11/2026 10:56:34 am

Thank you for clarifying. I also believe this is above the threshold of minimal combustible loading but I also understand that is an engineering judgement and was looking for second opinions.

Reply
Jack G
8/11/2026 09:41:35 am

Erik has it correct.
The space is non combustible.
You are adding combustible insulation and it’s not filled to the top.
It must be protected with sprinklers as the space becomes combustible.
I’m the 70 s energy crunch builders of commercial and residential construction used foam to conserve energy.
I watched a fire in a sprinklered building completely envelop the building from a fire in the vestibule. Foam board on the exterior beneath the siding. Housesame in less than 2 minute.

Reply
zackery geddies
8/11/2026 01:22:09 pm

take a look at Mineral wool such as Rock wool. It is non combustible and it has a thermal value.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top July '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 221
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    September 2026
    August 2026
    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT