In a four-story educational building, we have a large pipe chase that wraps around the men’s and women’s restrooms on each floor. The highlighted area in the attached sketch is the pipe chase area. The wall on the left (with the red arrows pointing at it) is a 1 hour rated shaft wall. All the other walls around the pipe chase are non-rated wall assemblies. There are doors (blue boxes) giving access to this area in three different locations. There isn’t any equipment or sources of ignition located inside the chase, just plumbing pipe.
While the area is not to be used for storage, we are concerned that the presence of the doors will allow people to do so. The Architect/Engineer has directed us not to protect this area with sprinklers. Are sprinklers required inside this chase or can they be omitted as directed by the A/E? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
16 Comments
Peter Howard
4/9/2026 06:11:04 am
There's a door. It will inevitably get used for storage, official designation or not.
Reply
Dan Wilder
4/9/2026 07:42:41 am
Yep...not just a single door, 3 doors and a lot of wall space available. I don't see an AHJ letting this one go. Maybe if those were only access panels it would be a better argument for omission.
Reply
4/9/2026 08:11:37 am
Why on earth do they need doors into this chase in the first place? Why not simply have the architect. Change these from doors to hatches and eliminate the whole concern.
Reply
KARLIN ROBERT JON
4/11/2026 12:56:32 am
this! raising the threshold of the door. eliminating a doorknobs. as well as limiting its size will help you win this argument that the access is prevents occupied use or storage - there are exemptions for pipe chases.
Reply
Glenn Berger
4/9/2026 08:11:54 am
What a waste of floor space. Sprinkler protection will be required.
Reply
Kevin
4/9/2026 12:48:55 pm
Hi Glenn,
Reply
Brett
4/9/2026 01:21:57 pm
Hi Kevin,
Glenn
4/9/2026 03:32:44 pm
Kevin is spot on - The wall hung units have a sizeable support carrier associated with them. Waste piping is a minimum of 3 inches and sloped.
Arthur Gould
4/9/2026 08:38:01 am
I agree with Glenn that sprinkler protection will be required.
Reply
Gary Sims
4/9/2026 09:02:26 am
Is this project being designed to meet NFPA 13 criteria? If so, that is for a "fully sprinklered" building... not a partially sprinklered building. They are calling it a 'chase', so why does it have doors? "for maintenance"... so then it's a maintenance space. They're trying to use naming convention in an attempt to avoid fire protection. I suggest you request the A/E obtain a formal variance/ authorization from the AHJ to omit fire protection. Make them do the work and provide copy to you. It protects them, you, and the owner. They are putting you in a bad position where you can't win. You could also size your pipe accordingly (to supply that area) and hit 'em with a nice change order when the AHJ makes you add fire protection.
Reply
Jack G
4/9/2026 09:41:12 am
Access panels will let them slip by but doors not.
Reply
Jose R Figueroa
4/9/2026 10:41:19 am
A.S. are not necessary. If those areas are ever used for storage, the principal should be reprimanded and a Housekeeping policy should be put in place. I have seen storage of cables, cardboard boxes, and old PCs in electrical rooms. That would not justify installing sprinklers. Without a proper Housekeeping policy, sprinklers may become ineffective, such as storing idle pallets in the aisles of rack storage.
Reply
Wes
4/9/2026 10:55:26 am
What's the code basis for this?
Reply
Justin
4/9/2026 04:13:33 pm
I agree with the other comments that in this current configuration, sprinklers are required in the space. However, the primary contributing factor is the doors accessing the space. If the doors could be replaced with hatches (or similar), I would classify this space as "Normally Unoccupied Building Service Equipment Support Area" per NFPA 101 and then see reason to qualify as a concealed space per NFPA 13 to omit sprinklers.
Reply
Jon N
4/9/2026 07:04:08 pm
In my former life as an AHJ, I supervised a state public school fire inspection program. Schools never have enough storage, and I can almost guarantee that eventually this space will be used for storage (especially convenient for paper products). Signage doesn't typically work well in schools or at least it isn't followed. Doors make it a room and storage is highly probable. Sprinklers should be installed.
Reply
Donnie
4/9/2026 07:34:08 pm
No doubt sprinkler protection would be required in accordance with NFPA 13 for the accessible space.
Reply