MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Sprinkler Req'd Below Duct 18-inches from Floor?

8/5/2024

7 Comments

 
What are the code references for obstructions greater than 4 feet wide (ductwork) but located only 18" from the floor?

We have a mechanical room with several large ducts 5 ft wide x 3 ft tall. The ducts are only 18" from the bottom of the duct to the finished floor.

Additionally, there is a second level of
a similar-sized duct that is mounted above, which leaves a 12" space between the top of the lower duct and the bottom of the upper duct.

Would we be required to install two levels of shadow protection under each duct, or are there provisions that allow sprinklers to be omitted if there is limited space below the duct?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments
Anthony Crispo
8/5/2024 07:52:38 am

NFPA13- 19&22ed 9.5.5.3.1.5
2016 - 8.5.5.3.1.5
Sprinklers shall not be required below noncombustible obstructions over 4 ft (1.2 m) wide where the bottom of the obstruction is 24 in. (600 mm) or less above the floor deck.

That being said if you're a contractor and your bid documents require it you may be protecting under low ducts anyway.  

Reply
Glenn Berger
8/5/2024 08:12:11 am

Thanks for the reference. I wish that NFPA folks would provide a commentary why they chose that number (24 inches in this case).

Reply
Anthony
8/5/2024 09:45:45 am

I would guess 2' is too short for storage as a bent/squatting person usually wouldn't have their face at 2' A.F.F. so it'd be unlikely to have a box of stuff. Similar to occupancy in an emergency/fire, it's an unlikely area to hide. Also NFPA generally choses round numbers for ease of use.

Dan Wilder
8/5/2024 01:54:44 pm

Took a bit but:

Committee Statement
Committee Statement: At some point it becomes ineffective to install sprinklers under obstructions that are close to the floor. The spray pattern of the sprinkler can't develop and the fuel load is so small that supplemental sprinkler protection isn't necessary.
Response Message: FR-90-NFPA 13-2013 The proposed value of 12” above the floor was revised to 24” based on minimum 18” required for sprinkler discharge pattern development plus deflector distance below obstructions.
Public Input No. 474-NFPA 13-2013 [New Section after 8.5.5.3.1.1]

Peter Howard
8/5/2024 08:22:33 am

From NFPA 13 (2016 edition):

8.6.5.3 Obstructions that Prevent Sprinkler Discharge from Reaching Hazard.
8.6.5.3.1 Continuous or noncontinuous obstructions that interrupt the water discharge in a horizontal plane more than 18 in. below the sprinkler deflector in a manner to limit the distribution from reaching the protected hazard shall comply with 8.6.5.3.
8.6.5.3.2 The requirements of 8.6.5.3 shall also apply to obstructions 18 in. or less below the sprinkler for light and ordinary hazard occupancies.
8.6.5.3.3 Sprinklers shall be installed under fixed obstructions over 4 ft wide. [There's your code path]
8.6.5.3.4 Sprinklers shall not be required below obstructions that are not fixed in place, such as conference tables.
8.6.5.3.5 Sprinklers installed under open gratings shall be of the intermediate level/rack storage type or otherwise shielded from the discharge of overhead sprinklers.
8.6.5.3.6 The deflector of automatic sprinklers installed under fixed obstructions shall be positioned no more than 12 in. below the bottom of the obstruction.
8.6.5.3.7 Sprinklers installed under round ducts shall be of the intermediate level/rack storage type or otherwise shielded from the discharge of overhead sprinklers.

--

That's the code path for standard spray upright/pendent sprinklers.

It's 8.7.5.3.2 for standard spray sidewalls. 8.8.5.3.2 for extended coverage upright/pendents. 8.9.5.3.2 for extended coverage sidewalls. 8.10.6.3.2 for residentials uprights/pendents 8.107.3.2 for residential sidewalls.

CMSA and ESFR have different rules.

I see no provision allowing for the omission, but if you find one, I'd be interested in reading it.

Reply
Franck
8/5/2024 09:21:39 am

This is a quite unusual situation.

You need to protected underneath the obstruction if there is something to protect.

If there is absolutely nothing underneath the obstruction that may be combustible or flammable, I don't see the benefit of providing additional sprinklers.
Some may say that you may find some storage one day undernath the ducts, but there is another rule in NFPA 13 asking to provide a minimum distance of 18 in. between the top of storage and the sprinkler deflector, which is again not possible in that configuration. So no possible storage allowed.

The only reason where you may need sprinklers underneath is if you are expecting a spill of flammable/combustible liquids with a pool fire...

Reply
Jack G
8/6/2024 12:27:38 am

I agree with Anthony . 24 inches the requirement. Believe me after a few years and maintenance is done there wil be filters, motors, and boxed replacement parts everywhere.
I believe the sprinkler is to be 3 inches minimum inside the duct.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT