MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Required Size of FDC Pipe for Larger Risers?

4/5/2021

8 Comments

 
NFPA 13 states that for hydraulically calculated sprinkler systems the fire department connection (FDC) pipe can be less than 4-inch diameter, but not less than the system riser.

What size should the fire department connection feed pipe be for a 6-inch riser, or an 8-inch riser?

Can the FDC pipe still be 4-inch for these larger risers?

I have some clients believe that 4-inch is the maximum no matter what, and some say if the riser is 6-inch or 8-inch that the FDC pipe needs to match the larger riser size.

​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Eric
4/5/2021 08:11:40 am

The code in NFPA 13 states that the size for the FDC is in accordance with ONE of the following. 4" minimum for fire engine connections is the most common and somewhat serves as a "rule of thumb" in the industry. In a hydraulically calculated system that is supplied by a smaller that 4 inch riser, the code referencing the smaller size comes into play. Then it is limited to the size of the riser servicing the system.

8.17.2.3* Size. The size of the pipe for the fire department
connection shall be in accordance with one of the following:
(1) Pipe size shall be a minimum of 4 in. (100 mm) for fire
engine connections.
(2) Pipe size shall be a minimum of 6 in. (150 mm) for fire
boat connections.
(3) For hydraulically calculated systems, the pipe size shall be
permitted to be less than 4 in. (100 mm), but not less than
the largest riser being served by that connection.

A.8.17.2.3 The purpose of a fire department connection is to
supplement the pressure to an automatic fire sprinkler system.
It is not the intent to size the fire department connection piping
based on system demand. For multiple system risers supplied
by a manifold, the fire department connection need not
be larger than that for an individual system.

Reply
Dan Wilder
4/5/2021 08:28:43 am

It depends.....I know right?

Which version and year are you referencing? I understand you referenced 13 but 14 has some specific language as to sizing & number of outlets required that will override 13. The 13-2007 Edition called out for a 2½" outlet per 250GPM of system demand (matches 14), later editions removed this requirement (in 13, 14 still has this requirement in 19'-7.12.3). Most of my AHJ's have adopted some variant of the sizing with most asking for a Siamese connection AND a Storz connection (4"-5" but they vary as well) for any system with a demand over 500GPM. At that point, we provide 6" piping regardless. I cannot say I've provided an 8" FDC supply unless a pump was present on some of our larger demand systems (those typically get into multiple Storz connections as well).

Officially (per 13-19'), sizing is based on 16.12.4 and can be less than 4" but not less than the largest riser being served. Any pumper connections shall be a minimum of 4". So with nothing more than NFPA to fall back to, match your riser size for the FDC supply piping. Bigger question is how many 2½" outlets are you providing for the larger systems?


It's a little outdated but a good start to all your FDC questions:

https://www.meyerfire.com/blog/a-fire-department-connection-cheatsheet

Here is a Research paper on the matter showing that a single 2½" inlet can provide over 500 GPM, a Siamese can get over 1500 GPM but anything more than 2 inlets was tested with a 6" pipe:

https://www.nfpa.org/-/media/Files/News-and-Research/Fire-statistics-and-reports/Suppression/RFFireDepartmentConnectionInletFlowAssessment.ashx

Reply
Monday Morning
4/5/2021 09:07:43 am

NFPA 13, 2016 8.17.2.3 says "The size of the pipe for the fire department connection shall be in accordance with one of the following:" (which means any of the options are acceptable). 8.17.2.3(1) states "Pipe size shall be a minimum of 4" for the fire engine connections." 8.17.2.3(3) states "For hydraulically calculated system, the pipe size shall be permitted to be less than 4 in., but not less than the largest rise being served by that connection." To the best of my knowledge, the intent of this section is to require a 4" FDC for any riser size but to allow you to use a smaller FDC for smaller risers. This means8.17.2.3(3) is giving the option of making an FDC smaller when possible but not intended to require larger FDC piping. A.8.17.2.3 explains that the intent is supplemental so assuming you have a reliable water supply, there is no reason to size an FDC based on system demand.

Many AHJs have their own FDC requirements which should be followed, but outside of AHJ modifications the intent of 8.17.2.3 is to require a 4" FDC with two 2.5" outlets (minimum) for fire sprinkler systems. Designing and installing 6" pipe definitely doesn't hurt anything, but NFPA 13 provides minimum standards which in this case is a 4" FDC.

Reply
NFPA 13, 2019
4/5/2021 09:22:20 am

It isn't as clear in earlier editions of NFPA 13, but the 2019 edition provides more guidance about the 4" minimum pipe size and two 2½" outlets.

NFPA 13, 2019 A.16.12.3.1 "The purpose of the fire department connection is to supplement the water supply but not necessarily provide the entire system demand. Fire department connections are not intended to deliver a specific volume of water."

NFPA 13,2019 A.16.12.4 "The purpose of a fire department connection is to supplement the pressure to an automatic fire sprinkler system. It is not the intent to size the fire department connection piping based on system demand. For multiple system risers supplied by a manifold, the fire department connection need not be larger than that for an individual system."

NFPA 13, 2019 16.12.3.1 "Unless the requirements of 16.12.3.1.1, 16.12.3.1.2, or 16.12.3.1.3 are met, the fire department connection(s) shall consist of two 2½ in. connections using NH internal threaded swivel fitting(s) with "2.5-7.5 NH standard thread," as specified in NFPA 1963."

Reply
Casey Milhorn
4/5/2021 09:53:48 am

Everyone covered it pretty well. The only thing I would add is to use some common sense as well. We just had a job with one of those "surprise" fire pumps (I think we've all had one or more of these before). Well the fire pump is going to be installed at the far end of the building from the current lead-in, which meant that the FDC has to feed all the way from the discharge side of the pump back to the front wall. This is a storage type occupancy with some larger GPM requirements. Per the standard, we could have technically provided a 4" main several hundred feet back to the front, but we know the friction loss would be extreme with even just 500 gpm flowing through it. We used a little common sense and upped the size to 6". Of course many times us contractors don't have the luxury of making things "better" but fortunately this was a change order situation and we had the freedom to make a good fire protection decision with the fire fighters in mind.

Reply
Dan Wilder
4/5/2021 11:22:38 pm

No close mains you could have tied into from the front of the building? We've tied into the primary (or secondary/dead main) if it matched the size of the riser up to that point (6" riser feeding a 4" primary = 6" FDC feed tieing into a 4" primary/secondary/dead main). We still provide checks to each system, just not at the riser room.

Reply
Casey Milhorn
4/6/2021 08:42:17 am

Unfortunately it's a multi-system building. We would have had to tie into 3 separate systems with checks on each one and the distances would have been more than the one bulk main. Great idea though and I've used that one before too.

Deborah H
4/6/2021 05:53:19 pm


Croker and Potter - FDC Siamese only come in 4" 5" & 6" (back, bottom or top feed) these products are all UL FM & used everywhere.

NFPA 13, 2016 8.17.2.3
Minimum is 4"

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Feb 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 30B
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT