|
We are working on a school project that needed a 1,000 gpm fire pump due to three standpipes.
We initially did a hydrant flow test and had a flow of 425 gpm with a static of 55 psi and residual of 50 psi when we started the design. By the time it went out to bid and the contractor performed their own test, they flowed 354 gpm with a static of 55 and a residual of 50. In the first test, we got 1215 gpm at 20 psi, and 1012 gpm in the second test. They went to turn on the pump and were only getting 368 gpm when the building inlet pressure was at 20 psi. We re-did the flow test to see what changed so drastically and again got a static of 51 with residual of 46 at 375 gpm, which would give us 1004 gpm at 20 psi. We have confirmed the two valves between the street and the building are fully open, and we only have about 50 feet of 8” pipe, so the pressure drop to the building is negligible, especially at 368 gpm. We are at a loss for what could be causing such a difference in pressure to the building and such a low flow. Has anyone ever run into an issue like this or have any suggestions of what else we could check out? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments
Pete H
8/25/2026 06:34:15 am
Is there any chance of a separate obstruction in the 8"? Or any other pipe damage?
Reply
Dan Wilder
8/25/2026 07:59:15 am
You have a theoretical 1000 GPM based on the assumption that the water supply remains consistent from ~400GPM through 1000 GPM....that is a long way to extrapolate data.
Reply
Anthony
8/25/2026 08:16:45 am
Why are the flow test results so low? Asking specifically why they're flowing such low volumes? Makes me think your feed taps out at ~1500gpm max. Do you even have fire flow high enough for this school? This is a serious infrastructure concern for any fire fighting in the area.
Reply
CASEY MILHORN
8/25/2026 08:20:26 am
Dan nailed it. This is why it's always good practice to flow the actual amount needed during your test, and for a sustained period of time (not just for a few seconds). Open up as many outlets as needed to get that 1,000 gpm, and do it as close to the actual connection point as possible. We hade one awhile back that was a 2,000 gpm pump, and we could only get 1,600+/- gpm out of a couple of hydrants. The extrapolated gpm at 20 psi was 2,300 gpm... cutting it very close, but the EOR signed off on it. During commissioning, it was more like 2,000 gpm at 18 psi, and 150% was out of the question of course. No one likes a surprise water storage tank, not good for anyone. Sometimes as the sprinkler contractor, you have to "help" the EOR, just make sure you don't set yourself up to be liable by "helping".
Reply
Glenn Berger
8/25/2026 08:27:29 am
As others have said - "Time of day" is a major factor. You did not state the type of area where the project is located. In a city, you have times of day where there is major amounts of water being used.
Reply
Jeremy
8/25/2026 08:55:46 am
I've had a wedge ("paddle") fall of the stem of the building OS&Y before. This then restricted flow and we were finally able to find the issue. It was a tricky scenario at first though.
Reply
Brian Gerdwagen
8/25/2026 08:58:11 am
Is there a golf course, farm, or industrial plant nearby that may be using a bunch of water? If you're really curious, use a pressure logger on a hydrant nearby for a few days to check the static throughout the day for a week.
Reply
danefre
8/25/2026 10:23:42 am
This happened because the project was issued to the contractor without first verifying that the water supply could support 100%—let alone 150%—of the rated flow at 20 psi. That is not a valid flow test.
Reply
Jack G
8/25/2026 11:00:41 am
You have forgotten the most important rules.
Reply
Jack G
8/25/2026 11:06:50 am
Also if old cast iron water mains supplying your new service ( examine the coupon) the old mains could have sediment and or corrosion affecting its size ) . There is a chart in NFPA showing the c factor to use on the pipe based on its age.
Reply
chad
8/25/2026 11:10:45 am
Its time of day or some other variable affecting the results. Assuming all else equal, others suggestions are a good place to start troubleshooting.
Reply
Sean
8/26/2026 10:50:44 am
All good comments here. If still looking for additional direction to investigate, verify your pump arrangement. Do you have a double check on the suction side of your pump? Is it restricting flow into the pump? Even differences across backflow manufacturers can cause huge losses and obstructions. Do you have OS&Y's and gate valves on the suction side, or butterfly type?
Reply
Michael Christensen
9/3/2026 01:48:34 am
I had a similar situation on a school that I did a couple years ago. We had the city check the PRV's that were installed. Initially they just checked the settings, eventually they checked the PRV and removed at least a fist-size of rust/gunk. This significantly increased the available fire flow.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop July '26 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
September 2026
PE PREP SERIES |
RSS Feed
