|
Has anyone ever conducted puff testing for a gas fire suppression system?
The owner is requiring us to perform this test, but I have never done it on previous projects. I checked NFPA 2001, and its requirements for flow testing are not detailed enough. I would like to know the specific procedures for conducting this test, as well as the key considerations to keep in mind. Ideally, I'd like to find a specification document or procedure to follow. Advance Thanks! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Glenn Berger
9/17/2025 08:12:33 am
Depending on what is being called the puff test --
Reply
Bob Ballard
9/17/2025 08:33:14 am
I have performed puff tests on gas fire suppression systems. The specific detailed procedures you're looking for should be found in the manufacturer's Design, Installation, Operation, and Maintenance (DIOM) manual for your particular clean agent system. Each manufacturer typically provides its own step-by-step puff test procedures, which are more detailed than those found in NFPA 2001.
Reply
Jose R Figueroa
9/17/2025 09:25:46 am
Refer to Factory Mutual DS 4-9
Reply
Mark Harris
9/17/2025 11:28:10 am
Great summaries Bob and Jose. Depending on what was available at time of test I have seen both air compressor and a nitrogen tank supply used. Have also seen balloons stretched over nozzles. At least for brands I dealt with don't recall manufacturer manuals having much more detail than NFPA 2001.
Reply
Jose R Figueroa
9/17/2025 11:58:14 am
Hi Mark, Thank you! I referenced and overly abbreviated “fluttering ribbons or smoke tracers,” “cylinder discharge port,” and “1-2 minutes per branch,” are common industry practices.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Oct '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
November 2025
PE PREP SERIES |
RSS Feed
