We have a project under NFPA 13 with different hazard classifications on the same floor. I’m designing a sprinkler system using the density/area method.
If different areas on the same floor have different occupancies and contents, for example, an OH1 workshop adjacent to an OH2 storage area, can the boundary between the two hazards be based simply on the different use/occupancy and materials present? Or does NFPA 13 require a specific physical separation or fire-rated compartmentation between them in order to use different hazard classifications? How stringent are these separation requirements? I’m not referring to the Room Design Method. Thanks in advance Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments
Pete H
8/24/2026 06:07:26 am
No physical barrier is required to separate OH1 and OH2.
Reply
Glenn Berger
8/24/2026 08:08:44 am
Pete's got the situation correct. Check with all of the Authorities on this one, as some officials will require physical (unrated) separations between hazard classes. The architect may also want to check with the applicable building code official.
Reply
Dan Wilder
8/24/2026 08:26:08 am
You'll want to apply the following;
Reply
Nimal Tissa Wijetunga
8/24/2026 09:53:49 am
It is indeed difficult to maintain physical separation by distance in a live situation practically.
Reply