Is the additional flow described by NFPA 13 27.2.4.2.5 (2019) based on the original minimum design area or the minimum area after modifications?
Say I have a light hazard system with low ceilings. The default minimum area is 1,500 sqft but is reduced to 900 per Section 19.3.3.2.3.1. The calculation on the sprinklers in that 900 sqft area results in 128 gpm total flow (not including the hose allowance). If the additional flow in 27.2.4.2.5 is based on the original 1,500 sqft, then I would need to add 22 gpm of extra flow on the main to get the minimum of 150 gpm running through the main. If the additional flow is based on the 900, then I'm already meeting the requirement of 90 gpm, and I can ignore the additional flow requirement. Similarly, we start at 1500 sqft in a dry attic system, but it needs to be increased to 2,535 sqft minimum due to the dry system and sloped ceiling. Will the minimum flow as per 27.2.4.2.5 be 150 gpm or 254 gpm? This sometimes comes up when using specialty attic sprinklers, which allow for fewer operating sprinklers in the calculation. It comes down to the definition of "minimum design area". Is this the original minimum area, or the modified minimum area? In my designs I've been defaulting to the larger of the two demands to be conservative, but what is the actual intent of this clause? I haven't found any discussions relating to the changing of the minimum design area. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Zachary Bishop
2/24/2025 08:30:59 am
The way this reads to me is the minimum design area as modified. Since, the "minimum" design area required is allowed to be increased / reduced in the situations you mention, it makes sense that the phantom flow requirement would change as well to match the requirements for the current situation.
Reply
Pete H
2/24/2025 09:06:02 am
I'd agree with Zachary and go with design area as modified.
Reply
Dan Wilder
2/24/2025 09:12:03 am
It is based on the "Minimum Design Area", so the final area after adjustments. I had to look back to the Ken Isman article that does reference an area reduction (high temp sprinklers for an Extra Hazard classification) which leads me to think it's the final minimum design area, not the starting point.
Reply
Casey Milhorn
2/24/2025 11:59:03 am
I agree with Dan and others. It's based on the final reduction or increase. As far as dealing with listed design approaches that are based on a listed system/product, then no, you would not add phantom flow. These listed design approaches have been tested and approved as listed.
Reply
Jack G
2/24/2025 03:30:52 pm
Here s the way i approach it.
Reply
Jack G
2/24/2025 03:58:38 pm
Looking at you dry attic with sloped roof, this area and sloped ceiling increases is for the “ dry system” and the “ ceiling slope”.
Reply
Jose figueroa
2/24/2025 05:37:58 pm
I read the exact same question on reddit.com.
Reply
Jose Figueroa
2/24/2025 07:11:11 pm
I'm sorry. I posted without finishing my post: If the total design discharge from the sprinklers is less than the minimum required discharge, this means there's insufficient water flow to properly suppress the fire. To compensate for this deficiency, additional water flow must be introduced.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Feb '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
March 2025
PE PREP SERIES |