I am working on a project with a diesel fire pump room that is Extra Hazard 2 (0.4 gpm / 2500 SF). The room is only 300 SF, which is well below 2,500 SF.
The 2022 Edition, NFPA 13 28.2.4.2.4, indicates following a set of steps shown in A.28.2.4.2.4. This section indicates that if the flow is less than the minimum required flow, then the difference in flow must be added to a node on the system. A.28.2.4.2.5 shows a picture example of where to add the flow. The current design has 4 sprinklers within the room, each discharging around 30 gpm ((0.4 gpm x 300 SF) / 4). When reviewing the shop drawings, 880 gpm was added to a node, increasing the system pressure to about 150 psi! How is NFPA 13 28.2.4.2.4 supposed to be accurately calculated within the hydraulic calcs? Do you create an imaginary system and, in this case, add 21 more sprinklers for a total of 25 (2500 / 100 SF per sprinkler)? Adding the 880 gpm to the system shown on the shop drawings and getting a required pressure of about 150 psi doesn't seem right.
10 Comments
Brett
10/16/2024 06:32:54 am
To answer your question, yes that is how it's supposed to be done as long as the flow is added at the appropriate point.
Reply
Anthony
10/16/2024 07:59:29 am
See below for the relevant code (NFPA13-16). You are correctly calculating just the hazard area as you have partitions separating the hazards.The point of the 'ghost flow' is to ensure the 'main' is sized for the hazard.So in this case add it jsut bast you 2 branch lines. I'm not an expert in hydracad or sprinkcad, not sure which you're using but you could just add a fake sprinkler or several flowing hoses to size the main there.
Reply
Dan Wilder
10/16/2024 08:11:29 am
Brett nailed it but some food for thought.
Reply
Mike Morey
10/16/2024 09:24:34 am
As usual Dan beat me to it, but this is the way to go. Room design method is not Density Area and thus not subject to phantom flow.
Reply
Brett
10/16/2024 09:49:53 am
The only caveat with the room design method is that the rating of the room has to be equal to or greater than the required water supply duration. If the room is EH2 (90 minute water supply required assuming it's electronically supervised) and it has 1 hour rated walls, then the room design method cannot be used.
Reply
Mike K
10/16/2024 03:18:29 pm
The room is 2 hr rated. Thanks for the input!
Reply
Jessica Lutz
10/17/2024 11:42:06 am
Wilder on point again. ....came here to comment on the Pump room 2-hr rating requirement.
Reply
Jack G
10/16/2024 09:03:47 am
MeyerFire 5/7/2020 indicates the design density should be. .25 for a diesel fire pump. I would try submitting that wit “ room design method”.
Reply
Jesse
10/16/2024 09:08:14 am
I love these threads that make you think. Topics like these are ones I kind of forget about until we need to do it.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Feb '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
March 2025
PE PREP SERIES |