A new-construction church is to contain a main sanctuary and stage, complete commercial kitchen with lounge seating area, and a connected enclosed parking garage. What is the most hazardous fire sprinkler occupancy for this facility? a. Light Hazard b. Ordinary Hazard Group 1 c. Ordinary Hazard Group 2 d. Extra Hazard Group 1 Solution | Posted 07/17/20
6 Comments
Anthony
7/16/2020 07:45:40 am
B - Kitchen and Parking Garage are OH Group 1 per NFPA 13 sec. A.4.3.3. All others are Light Hazard.
Reply
RPM
7/16/2020 10:37:59 am
C. Stage - OH Group 2.
Reply
DAT HUYNH
7/16/2020 12:26:54 pm
OH II only stage is over 1,000 square feet. If not, then the most hazardous occupancy is OH I. Not sure!!!
Reply
Bobby Velasquez
7/31/2020 09:47:43 am
Where did you find that requirement?
Reply
SK
7/16/2020 01:48:29 pm
C. Ordinary Hazard Group 2
Reply
JOE
7/16/2020 06:45:36 pm
C
Reply
Leave a Reply. |
Free SignupSubscribe and learn something new each day:
CommunityThank You to Our Top
February '21 Contributors!
Your PostThe ToolkitSprinkler Designer or Engineer?
Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more: Filters
All
Archives
March 2021
Daily
Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
Exam Prep2020 PE Prep Guide
(Available Now!) PE Prep Series
(Available Now!) 2020 PE Prep Series
Current Leaderboard (Click to enlarge) PE Problems
Visit July-October for daily Fire Protection PE Exam sample questions.
Solutions are posted the day after posting. Comment with your solutions, questions or clarifications. Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves. |