I have a wet standpipe system served by a vertical turbine pump using an underground tank as a water supply. This is standpipe only, with no sprinkler system, and is in a remote location with no municipal water source.
NFPA 14-2013, Section 5.6, and similarly NFPA 14-2024, Section 9.7, require a listed waterflow alarm. In this circumstance, the only way to get waterflow is for the pump to work, since the water source is a buried tank. A signal is sent to the fire alarm should the pump activate, so having a separate waterflow alarm is redundant and doesn't really add anything here. Is there something I could be missing where the waterflow alarm adds to the system? Otherwise, we would like to omit it. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Brett
10/28/2026 07:12:25 am
The only additional value a flow switch would add is leak detection. A small leak could theoretically trip the flow switch while only requiring the jockey pump to run to keep the pressure up.
Reply
Chad
10/28/2026 07:45:16 am
Yes, this, allows the water in the pipe to be supervised.
Reply
Dan Wilder
10/28/2026 07:40:28 am
The only thing I can think of is "Does pump run=waterflow" 100% of the time? Typically, no, ITM activities weekly and monthly negate this.
Reply
Jesse
10/28/2026 08:21:36 am
The pump running does not necessarily mean water is flowing. I think we've all seen times where a pump ran for an extended period and dended up getting fouled.
Reply
Jack G
10/28/2026 09:03:52 am
Along with the water flow to supervise, I would hope there is a magnetic level detector switch/ rod that sends the water level to the supervising panel.
Reply
Streeter Stirling
10/28/2026 11:21:41 am
To go against the grain here, you might be able to get AHJ approval to remove it with reasonably low risk.
Reply
Joe
10/28/2026 12:16:52 pm
Are there notification appliances within the building that the building occupants would benefit from the waterflow alarm, otherwise I can relate to the no value added logic.
Reply
Randy Kimbro
10/28/2026 12:18:25 pm
As an AHJ, we always prefer to have an exterior water flow horn strobe. As our fire apparatus arrive, that horn strobe shows definitely that water is flowing somewhere. Even without sprinklers as you mentioned, the horn strobe confirms water is flowing and we need to take some action, probably quickly, to avoid flooding the facility.
Reply
Joe
11/10/2026 08:48:56 am
When will a standpipe flow water without the fire department already being on scene?
Reply
Randy Kimbro
11/11/2026 02:13:56 pm
From NFPA 25 (2026)
robert karlin
10/28/2026 07:15:06 pm
The pump run alarm should be set to a supervisory alarm. is is basically a supervisory alarm to tell the owner the pump is operating for whatever reason - testing, leaking, bad sensors et al, The water flow alarm should be installed downstream the flow test loop/outlets and signal a waterflow alarm (fire) indicating water is flowing in the facility. They have 2 different purposes - the supervisory alarm is to alert ITM concerns to prevent a very expensive fire pump from running for days until failure - the water flow alarm is to alert first responders that a water is flowing - most likely due to a fire.
Reply
Mark
10/29/2026 10:05:19 am
This is the original poster. This was submitted a while back and we already decided to add the flow as a way to alert for leaks.
Reply