I have a 2-story space with a mezzanine. The ceiling above the mezzanine is unconditioned. I need to sprinkler the space and plan to do so using two rows of sidewall sprinklers along the ceiling, pointing towards the middle of the opening.
There is an obstruction running down the middle of the ceiling. (See diagram below for a section view of the space.) Using Figure and Table 10.3.6.1.3 from NFPA 13 2019, the sidewall sprinklers would need to be spaced 8' to 8'-6" away from the obstruction, which isn't possible. However, I'm not sure if Figure 10.3.6.1.3 applies to my situation, given that I am spraying from both sides of the obstruction. Section 10.3.6.1.5 might apply to my situation, but the wording makes it seem like it is referring to obstructions along the same wall the sprinkler is on. Does Section 10.3.6.1.5 apply here? Thanks in advance! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Pete H
2/19/2026 06:13:09 am
It doesn't apply. You're spraying from both sides of the obstruction.
Reply
Dan Wilder
2/19/2026 06:21:35 am
The committee did a good job identifying when the sections applied to obstructions along the same wall or not. Section 10.3.6.1.5 does not say "same wall" thus it would apply to any wall, same, adjacent, or opposite, provided that the space below the obstruction, as measured from the two sprinkler centerlines, is still within the coverage area of the sprinkler.
Reply
Glenn Berger
2/19/2026 08:14:23 am
Your proposed sprinkler placement with respect to the obstruction meets the requirements set forth in NFPA 13.
Reply
Jack G
2/19/2026 08:22:27 am
Stagger the rows.
Reply
Donnie
2/19/2026 06:50:16 pm
No obstruction. The discharge spray pattern will cover beneath the so called obstruction.