The IBC section 403.3.3 requires an automatic on-site secondary water supply for high-rise buildings in seismic zone C or greater.
Does NFPA have a similar requirement for on-site water storage in a seismic zone? All I can find are the bracing requirements in NFPA 13, but I am not seeing anything in NFPA 101 or NFPA 5000. Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments
Anthony
6/16/2025 08:11:23 am
As far as I'm aware this is only an IBC requirement. However it is worth looking in to the high rise requirements of 14 and 20.
Reply
Todd E Wyatt
6/16/2025 08:30:52 am
IBC is the scoping Code WHERE an automatic sprinkler system (ASPS) is required to be installed based on Occupancy Classification (OC) and/or special buildings or hazards while NFPA 13 is the referenced standard by the scoping Code as to HOW the ASPS is to be designed, installed, inspected, and maintained.
Reply
Robert J Bennett
6/18/2025 11:31:13 am
The IBC requires the secondary supply and provides 2 ways to accomplish it.
Reply