NFPA 13 is clear about a limit of 10 feet under a building before pipe needs to turn up and into a building (with exceptions for trenching).
What about pipe exposed within a basement? Is there a limit to how far an underground service can run exposed within the building before the system riser? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Dan Wilder
2/21/2025 08:00:27 am
Couple things come to mind on this...
Reply
Glenn Berger
2/21/2025 08:09:57 am
Concur with the Dan's write-up. I also want to add that the 10 foot rule is limit the number of pipe segments and fittings that are located below the building and therefore be inaccessible.
Reply
Chad
2/21/2025 08:14:37 am
I would explain to the owner how hazardous it would be to have pipe that they cannot shut off, running through their building more than a few feet. As an AHJ, I might determine that as a hazard and tell them they have to have a shut off/flow switch as it enters…. no one can tolerate a a large main flowing water with no alarm connected to it…. You could fill up a basement pretty quick with no warning.
Reply
Christopher Nelson
2/21/2025 09:25:53 am
As a designer and now AHJ, I would accept more than 10 ft if its accessible. Thats the whole point of allowing it if its trenched, accessibility.
Reply
Christopher Nelson
2/21/2025 09:27:43 am
Also the point of yard PIVs, yard/street boxes, etc to shut off the section before the riser.
Reply
Jack G
2/21/2025 10:40:10 am
Sometimes a specific type of piping material is specified by the water company. Example— Chester water, aqua American water , DI pipe is specified all the way up to the water meter and or the BFP. So depending on how close to the service wall, depends on how much. ( uniflanged for DI pipe )
Reply
Jesse Cecil
2/21/2025 11:33:03 am
Some good comments here. I'd add a couple things.
Reply
Anthony
2/24/2025 06:53:47 am
ALWAYS put a "city valve" on a stub up.
Reply
Ryan Hinson
2/21/2025 11:51:17 am
NFPA 24 (2022) Section 10.1.4 allows the the underground piping to daylight into a building through a slab or wall up to two feet regardless of pipe type. Beyond this, one must use those pipe types allowable for aboveground service per NFPA 13 (2022) Table 7.3.1.1. Though allowable per code, I would NOT recommend extending the UG pipe if PVC or HDPE is used since these pipes are only listed for use in FP for underground. The mfgrs' own listings indicate this.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Feb '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
March 2025
PE PREP SERIES |