In an electrical room with transformer panels and equipment, sprinklers are required.
What type of baffle would you use to prevent direct spray on the panels (preaction system)? In the past, I was permitted to use “light bulb shields” that would snap right on (similar to an automotive under-the-hood mechanic light shield), and AHJs had no objections. Spray was definitely in one direction. Would this fit the NFPA definition of a baffle? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments
chad
10/19/2026 08:23:37 am
It is not a code requirement that a head cannot spray into/on electrical equipment. You cant run pipe above them, but that is a separate issue.
Reply
chad
10/19/2026 08:32:28 am
Also I guess it depends on what cycle you are on, excerpt from the 2022 handbook commentary on 9.2.6:
Reply
Todd Wyatt
10/19/2026 09:10:36 am
Per the scoping Code (e.g. IBC-2024), “TRANSFORMER ROOMS separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS” can be EXEMPT from protection of Automatic Sprinkler Systems (ASPS) per 903.3.1.1.1 (see below) if “protected with an approved automatic fire detection system ... that will respond to visible or invisible particles of combustion.”
Reply
Streeter
10/19/2026 11:37:33 am
Conceptually, I would not want to shield the equipment without a very good reason. At the end of the day if the transformer catches fire we want the sprinkler to put the fire out, even if it is electrical equipment.
Reply