MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Is Electronic Monitoring for Sprinklers Required?

8/27/2024

11 Comments

 
I have an older class B Mercantile space that is sprinklered but not alarmed. The last tenant was a large pharmacy chain that monitored their own fire alarm or sprinkler systems. When they left they removed the alarm panel.

The tamper and flow switches are still there, as well as an exterior electronic flow bell.

Does this sprinkler system require electronic monitoring?

Currently they have nothing monitored. I would like it to be monitored, but need something to back me up. We adopted the 2021 I-Codes and 2015 NFPA 101 (Statewide).

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments
Glenn Berger
8/27/2024 08:07:24 am

The requirement for "electronic monitoring" would come from the AHJ, insurance, locality needs.

Reply
Pete H
8/27/2024 08:13:12 am

When you say "exterior electronic flow bell" is this an electric bell or is this a pneumatic water motor gong on the outside?

Either way I think the code path you're looking for is NFPA 101 (2015) 9.6.4.2

When emergency forces notification is required by another section of this code, the fire alarm system shall be arranged to transmit the alarm automatically via any of the following means acceptable to the authority having jurisdiction and shall be in accordance with nfpa 72, national fire alarm and signaling code:
1) Aux. fire alarm system
2) Central station fire alarm system
3) proprietary supervising station fire alarm system
4) remote supervising station fire alarm system

Reply
David Kendrick
8/27/2024 08:23:49 am

Pete, what is a “pneumatic” water motor?
Wouldn’t it be hydraulic? Water powered?

Reply
Pete H
8/27/2024 08:38:54 am

Hydraulic is correct.

Franck
8/27/2024 08:26:41 am

As indicated by Glenn, the requirement will normally come from the AHJ or any otrher specific request/regmlementation.

But the decision may be yours as well. Especially if local requirements are not very demanding (and satisfied with a local unattended alarm only).

Would you rely on somebody in the street hearing the outside water gong to call the Fire Department? Even if it happens in the middle of the night during the weekend?
And what would the FD does if there is nobody available in the facility?
It might be wise, when you have automatic fire protection, to have the alarm sent to a constantly attended location, able to make the right decision.
Would you do the same with intrusion alarm?

Reply
Sean H
8/27/2024 08:51:10 am

I believe your journey could start in Chapter 9 of the IBC.

Section 901.6.1 - Automatic sprinkler systems shall be monitored by an approved supervising station. Two exceptions are automatic sprinkler systems for 1-2 family dwellings, and limited area systems in accordance with Section 903.8.

How would the sprinkler system be monitored you ask - through the use of a dedicated function sprinkler/supervisory service monitoring system and communicator that doesn't need to comply with the requirements of a full fire alarm system. Jump to section 903.4 for more details

As far as what that monitoring entity needs to be (central station, remote supervising, proprietary etc), that would be the discussion with the AHJ to determine the extent of what they approve.

Reply
Jack G
8/27/2024 09:22:42 am

Sean has it.
If a new panel is installed i would suggest new devices so that everything matches.
I d even suggest replacing the wiring.

Reply
Todd E Wyatt
8/27/2024 09:23:50 am

Your initial review should start with the scoping Code (e.g. IBC-YYYY?) that was applicable/adopted when the building’s Drawings were initially reviewed by the AHJ.

If the Group M Mercantile building was required to be MONITORED BY AN APPROVED SUPERVISING STATION, as IBC-2018 (example) states below :

IBC-2018
Chapter 9 Fire Protection and Life Safety Systems
Section 901 General
901.6 Supervisory Service
Where required, fire protection systems shall be MONITORED BY AN APPROVED SUPERVISING STATION in accordance with NFPA 72.
901.6.1 Automatic Sprinkler Systems
Automatic sprinkler systems shall be MONITORED BY AN APPROVED SUPERVISING STATION.
Exceptions:
1. A supervising station is not required for automatic sprinkler systems protecting one- and two-family dwellings.
2. Limited area systems in accordance with Section 903.3.8.

… then the existing building STILL requires it.

The scoping Code adopted at the time may include provisions for the termination of monitoring system for the Automatic Sprinkler System similarly for Fire Alarm monitoring :

IBC 2018
907.6.6.2 Termination of Monitoring Service
Termination of fire alarm monitoring services shall be in accordance with Section 901.9 of the International Fire Code.

IF the existing building was altered since it was initially occupied, the next review would be with the currently adopted International Existing Building Code (IEBC) to determine the scoping requirements for the existing Fire Protection System based on its Level of Alterations (1, 2, and/or 3) and/or Change of Occupancy.

The intent is for the initially approved Fire Protection System to NOT be altered (e.g. “last tenant was a large pharmacy chain that monitored their own fire alarm or sprinkler systems … when they left they removed the alarm panel”) without approval by the AHJ.

Reply
Randy Kimbro
8/27/2024 11:32:48 am

As an AHJ, sprinkler MUST be electrically supervised ...

2021 International Fire Code (IFC)

903.4 Sprinkler system supervision and alarms.
Valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and waterflow switches on all sprinkler systems shall be electrically supervised by a listed fire alarm control unit.

Exceptions:

1.Automatic sprinkler systems protecting one- and two-family dwellings.

2.Limited area sprinkler systems in accordance with Section 903.3.8.

3.Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided.

4.Jockey pump control valves that are sealed or locked in the open position.

5.Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position.

6.Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position.

7.Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position.

8.Underground key or hub gate valves in roadway boxes.

Reply
Jesse
8/27/2024 12:05:06 pm

While it's AHJ driven, the short answer is yes. They'll need a riser monitoring panel.

Reply
Conrad
8/27/2024 01:37:22 pm

In my NFPA jurisdiction, I have seen similar where either fire alarm or electronic supervision for fire sprinkler was removed by the tenant when they left without permission of the AHJ. NFPA model code requires a permit for the modification or removal of a fire protection system.

If a permit was not applied for, this may subject the property owner to a fire code violation if the tenant space is occupied.

Even if electronic monitoring / supervision was not required, once it was installed it must be maintained unless permission granted by the AHJ. https://www.meyerfire.com/daily/ok-to-leave-non-required-sprinklers-in-place

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top May '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT