|
I have a project I'm working on for a data center, and the owner is requesting a Hazard Mitigation Analysis (based on NFPA 855). I'm trying to see if NFPA 855 is applicable since it relates to energy storage systems (ESS).
The end user will have a UPS installed in each rack instead of a central UPS, and each rack will only be 0.55 kWh. FM is also applicable in this case, but FMDS 5-32, Section 2.3.1.4.2 indicates that if your in-rack UPS exceeds 20 kWh, then that pushes the system into an ESS and FMDS 5-33. But, NFPA 855 indicates that if aggregate quantities within the fire area exceed 20 kWh (which we would be for the data hall), then it's defined as an ESS. Is the in-rack UPSs below 20 kWh are actually defined as an ESS or if they're just information technology equipment and NFPA 855 doesn't apply? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments
Joe Mc
7/9/2026 08:48:00 am
IFC 2024 section 1207 and related sub section will mostly govern,
Reply
Jack G
7/9/2026 08:53:25 am
Per NFPA an ESS is an energy storage system. It stores energy and releases it later. That usually means lithium ion batteries. These batteries stack together in large racks for hones or businesses.
Reply
Michael Knott
7/9/2026 12:15:12 pm
Appreciate it!
Reply
Jocelyn
7/9/2026 08:59:13 am
FMDS 5-32, the IFC, and NFPA 855 all scope their documents a little differently. I agree with your assessment of FMDS 5-32. The IFC also doesn't specify aggregate capacities for Section 1207 applicability, so I would argue Section 1207 doesn't apply to this case either.
Reply
Michael Knott
7/9/2026 12:13:53 pm
Thanks! If you're the same Jocelyn in the MeyerFire University series on ESS, thank you very much! I started watching those as I was banging my head against the wall and it helped to clear some things up.
Reply
Jocelyn
7/9/2026 12:31:06 pm
It's me!
Dan Wilder
7/9/2026 09:03:48 am
I have seen this on a couple DC's lately and even with the dispersion or individual ESS components (ITE and the separate ESS components), the aggregate total within area drives the overall design. The designs have been able to utilize information specific to testing results that were provided to the AHJ by the owner as allowed in IFC 1207 for density, area, and configuration requirements and they were allowed to go with a lesser density however the area remained + applicable increases like dry/preaction, air velocity limits...
Reply
Michael Knott
7/9/2026 12:11:12 pm
Thanks!
Reply
Ricardo Gonzales
7/13/2026 01:02:11 pm
You should also check with the Owner and see IF they've done full scale testing. That would and should be listed and identified in an HMA which would allow limited sprinkler and detection schemes.
Reply
Raymond Armas
7/15/2026 04:55:14 pm
I believe the Threshold Quantities in table 1207.1.3 is based on the aggregate energy capacity of all ESS in the fire area. Section 1201.3 provides insight to this measurement concept for the Maximum Allowable Quantity threshold in Table 1207.5. I would have to assume the use of aggregate capacity would be the same in establishing the applicability of Threshold Quantities.
Reply
Jocelyn
7/15/2026 05:56:30 pm
I don't agree with that interpretation of IFC Section 1201.3. The section header is for "Mixed system installation" and the section considers the aggregate sum of all ESS types (PV, Fuel Cell, electrochemical ESS) with regards to their respective MAQs, in the event that multiple types of ESS are in the same fire area.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop July '26 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
August 2026
PE PREP SERIES |
RSS Feed
