GC asked us to add (1) head to a dentist's office closet where they store the nitrous tanks. Not a big deal, done it before tapping off the domestic line. The AHJ asked for calcs to prove it will work. The existing building is not sprinklered.
What are your thoughts on this? Is there a way to prove it's workable? Is there a standard that stipulates what is and what's not acceptable? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Pete H
6/25/2026 06:05:29 am
Well we're definitely in a grey area. But AHJ made the request.
Reply
Brian K. Fain
6/25/2026 08:29:12 am
A word of caution, we have been required to install a separate backflow preventer for this one sprinkler head in the past.
Reply
Kelley Stalder
6/25/2026 08:40:54 am
Isn't a backflow preventer required anyway for a dental office?
Reply
Brian
6/25/2026 08:45:54 am
Yes. They had one on the domestic feed (which we tapped into), but the AHJ required a separate one for our sprinkler head and piping.
Ben F
6/25/2026 08:32:32 am
I would think this falls under the limited area sprinkler system requirement in the IFC, which would require a calculation per NFPA 13. Not sure where you are located or what's locally adopted, but 2024 IFC section 903.3.8 lists the requirements. My concern would be if this is classified as a med gas room, which would be OH2. Limited area sprinkler is limited to LH and OH1.
Reply
Glenn Berger
6/25/2026 08:44:59 am
I actually like the AHJ asking this comment. Just want to make sure that there is sufficient pressure such that water will flow from the sprinkler.
Reply
Blaine
6/25/2026 08:51:51 am
I’ve always thought that you had to do the whole building and can’t just put in a sprinkler wherever you wanted. Ref NFPA 13 2022 1.3.2. For me it came up when I wanted to put some residential sprinklers in my shop where I had easy access to the water lines in the overhead.
Reply
Jack G
6/25/2026 11:20:54 am
Tyco makes a domestic water shut off valve (RSV-1) installed after the split to the single sprinkler. It prioritizes the flow to the fire system so the full flow and pressure is available.
Reply
Wes
6/26/2026 08:04:27 am
I believe the Tyco RSV-1 is only listed for residential use.
Reply
Jon N
6/26/2026 11:26:09 am
As a former AHJ, we required many "limited area sprinklers" to protection a localized hazard (boiler rooms, paint booths, flammable liquids rooms, etc.). These would typically be 1-2 sprinklers off the domestic supply. Since this was potable water, they would often use copper lines. Most often these were "pipe schedule" designs - up to two sprinklers supplied by 1-inch copper per NFPA 13 (2016 edition) - Section 23.7.2.2.1.
Reply
Mark Harris
6/30/2026 02:31:33 pm
Comments have covered most of my thoughts and Jon N well summarized what we did long time ago when BOCA code required sprinklers in a specific area (plus small basements).
Reply
David L Miller
7/1/2026 10:55:06 am
RE: NFPA 101:9.7.1.2
Reply