MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

How to Select the Coverage Area for a Sprinkler?

1/28/2026

10 Comments

 
We have an apartment, protected by a birdcage residential sprinkler system per NFPA 13. We need to calculate the most demanding 4 sprinklers, which end up being 3 in the room and another on the back side of one of the 3 (this apartment has the longest throw).

I need to calculate the most demanding of the two (1) flow rates per the approval chart in the sprinkler's listing, or (2) calculate based on 0.10 gpm/sqft over design area according to 8.5.2.1 or 8.6.2.1.2.

Can I choose 8.5.2.1 or 8.6.2.1.2? Or is it the more demanding of 8.5.2.1 or 8.6.2.1.2, and then compare that to the flow rates per the approval chart in the sprinkler's listing?

Thank you in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Pete H
1/28/2026 09:40:35 am

You're doing a residential 4 head calc and it's an NFPA 13 building not a 13R?

Reply
Brett
1/28/2026 10:45:38 am

In NFPA 13 it's still a four head calc but it's the four most demanding adjacent sprinklers regardless of the locations of walls. 13R tells you to break up the calcs by compartment.

Reply
Kevin Wilson
1/28/2026 01:54:13 pm

Yes. Using residential in the individual apts so calculating 4 most demanding

Reply
Shane
1/28/2026 10:13:59 am

I am not familiar with "birdcage" residential sprinkler system. Can you explain?

Reply
Moderator
1/28/2026 10:39:05 am

Great question. "Birdcage" is a zoning setup where the top-most floor of a building is served with sidewall sprinklers, each from the level below.

So say this is a 4-story building, the topmost 4th floor level are served from the floor below.

The runs of vertical pipe between the 3rd and 4th floor would give a "birdcage" look of vertical pipe runs if they were viewed as a whole system.

Technically, birdcage 'could' mean that 'all' floors are served in this manner (one zone, all sidewalls from vertical pipe runs), but we've generally taken it as meaning only the topmost floor is served in this way. That'd be 'whole-building birdcaged' versus 'top floor is birdcaged.'

Reply
Brett
1/28/2026 12:15:29 pm

We use the term for 13R buildings that are supplied by one system with multiple vertical risers tied into each floor's horizontal cross main. It resembles a bird cage if you sketch it out.

Reply
danefre
1/28/2026 10:48:49 am

See NFPA 13 (2013) Section 11.3.1.3 and then look at the clarification/addition on the NFPA 13 (2019) section 19.4.1.3. Even in 2013 you are permitted to do area of compartment divided by number of sprinklers for residential sprinklers. It was not very clear but always there.

Short answer, compartment over 800sqft (not meeting small room rule definition) you use the regular S x L per 8.5.2.1. That's a bit rare to have apartments with compartments over 800sqft in NFPA 13. If it's a corridor we usually do QR or Special application corridor sprinklers. If you do have this condition, this will probably the most demanding.

Compartment under 800sqft (meeting small room rule definition) you use the area of the compartment divided by the number of sprinklers for your demand, as per 8.6.2.1.2. This is the most common scenario.

You don't freely choose between 8.5.2.1 and 8.6.2.1.2, you pick whichever applies based on the compartment. Again the 2019 edition clarifies that better.

In practice, the manufacturer's data sheet (approval listing) is most demanding in most cases in NFPA 13 but you still have to prove it.

Reply
Kevin Wilson
1/28/2026 01:59:51 pm

Thank you for your reply!

Reply
James Art
1/28/2026 03:52:30 pm

Q. In the current 2025 editions, are FLOOR CONTROL valves required?
Perhaps this is a IFC requirement?

Reply
Brett
1/29/2026 06:38:11 am

They are required by NFPA 13 if the building is more than two stories although the top floor can be supplied by the piping on the floor below.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT