|
We have an apartment, protected by a birdcage residential sprinkler system per NFPA 13. We need to calculate the most demanding 4 sprinklers, which end up being 3 in the room and another on the back side of one of the 3 (this apartment has the longest throw).
I need to calculate the most demanding of the two (1) flow rates per the approval chart in the sprinkler's listing, or (2) calculate based on 0.10 gpm/sqft over design area according to 8.5.2.1 or 8.6.2.1.2. Can I choose 8.5.2.1 or 8.6.2.1.2? Or is it the more demanding of 8.5.2.1 or 8.6.2.1.2, and then compare that to the flow rates per the approval chart in the sprinkler's listing? Thank you in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Pete H
1/28/2026 09:40:35 am
You're doing a residential 4 head calc and it's an NFPA 13 building not a 13R?
Reply
Brett
1/28/2026 10:45:38 am
In NFPA 13 it's still a four head calc but it's the four most demanding adjacent sprinklers regardless of the locations of walls. 13R tells you to break up the calcs by compartment.
Reply
Kevin Wilson
1/28/2026 01:54:13 pm
Yes. Using residential in the individual apts so calculating 4 most demanding
Reply
Shane
1/28/2026 10:13:59 am
I am not familiar with "birdcage" residential sprinkler system. Can you explain?
Reply
Moderator
1/28/2026 10:39:05 am
Great question. "Birdcage" is a zoning setup where the top-most floor of a building is served with sidewall sprinklers, each from the level below.
Reply
Brett
1/28/2026 12:15:29 pm
We use the term for 13R buildings that are supplied by one system with multiple vertical risers tied into each floor's horizontal cross main. It resembles a bird cage if you sketch it out.
Reply
danefre
1/28/2026 10:48:49 am
See NFPA 13 (2013) Section 11.3.1.3 and then look at the clarification/addition on the NFPA 13 (2019) section 19.4.1.3. Even in 2013 you are permitted to do area of compartment divided by number of sprinklers for residential sprinklers. It was not very clear but always there.
Reply
Kevin Wilson
1/28/2026 01:59:51 pm
Thank you for your reply!
Reply
James Art
1/28/2026 03:52:30 pm
Q. In the current 2025 editions, are FLOOR CONTROL valves required?
Reply
Brett
1/29/2026 06:38:11 am
They are required by NFPA 13 if the building is more than two stories although the top floor can be supplied by the piping on the floor below.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Dec '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
February 2026
PE PREP SERIES |
RSS Feed
