MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

How to Remedy Constant High Static Pressure?

5/20/2020

5 Comments

 
My fire sprinkler system was poorly designed. Static fire water pressure is constantly at or above the relief valve rating. This causes the valves to constantly discharge. I can't rebuild the fire system.

Can I put two valves in parallel or in series to reduce pressure? Would that invalidate the system?

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments
Dan Wilder
5/20/2020 08:17:29 am

Is the system working pressure above 175 PSI or is it below 175 but the relief valve continues to leak?

If the system working pressure is below 175 PSI, change the relief valve to a higher pressure. Note taken from AGF site:

"Standard relief valves are required to OPEN in a range of pressure between 90% and 105% of their rating. The valves are required to CLOSE at a pressure above 80% of that rating." This means a 175 PSI valve will start to open at 158 PSI. Putting a 195 PSI valve on there would allow for a 175 PSI opening pressure.

If you have a working pressures above 175 there are two options (well possibly 3):

Change out all the sprinklers to a 300# rated sprinkler and verify all other system components are rated for the higher actual static pressure (some threaded fittings and valves carry a lower rating, pipe/couplings).

Provide a Pressure Reducing assembly per the MFG's requirements (typically a large valve with a smaller valve for low flow conditions). You may need to provide redundancy (dual setups). The system will need to be recalculated to prove the lower pressure is still able to provide the needed supply for the building occupancy and hazard.

The third is have the incoming supply pressure be reduced by the water municipality. This would affect every building on that supply and not likely an option but an option if it only supplies that building.

Reply
Jonathan Sullivan
5/20/2020 08:34:12 am

Awesome explanation Dan. Also this was addressed from an installation standard perspective here:

https://www.meyerfire.com/daily/relief-valve-for-wet-pipe-sprinkler-systems

if anyone wants to read.

Reply
Casey Milhorn
5/20/2020 04:15:23 pm

Yup, Dan nailed it. Surprisingly many of the sprinklers, valves, fittings, and couplings are rated above 175 psi nowadays, compared to when I started in the biz. You might already be okay, as Dan mentioned, to just simply swap out the pressure relief valve to a higher pressure. Next I would talk to the City and see what they can do to help out if the first option doesn't work. Pressure regulating/reducing valves would be my last resort. They add inspection and testing costs to you annually, are prone to failure, and could lead to early repair/replacement costs.

Reply
Stephen Aikey
5/20/2020 12:50:39 pm

Not sure I would be so quick to blame the Sprinkler Design! Sounds like the relief valve is working as designed. Would like more information as to where the high pressure supply is coming from?

Reply
Pete D
5/20/2020 08:15:31 pm

If the sprinkler design required 175 psi at a 40 ft roof elevation, it would need to have roughly 192 psi at ground level. If you had a 185 psi rated relief valve it would constantly leak. You need to look at the sprinkler hydraulic calcs to see what is required at the pump discharge, and look at the safety margin. If the additional pressure is needed in your installation, a higher rated relief valve can be installed on each riser. If the added pressure isn't needed, it may be as simple as dialing back the off theeshold on your jockey pump controller to fix all systems leaking.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About