MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

How to Meet Highrise Second Supply Req'ment?

8/1/2024

4 Comments

 
Our high-rise facility consists of apartments, condominiums, retail on the bottom floor, restaurant tenants on the top floor, and (3) levels of underground parking. We are 9 stories tall out of the ground.

They have great water pressure at the site with 140 static
 and 118 residual, flowing about 1,900 GPM, but with our floor-to-floor distances, I cannot get 100 PSI at the top of my standpipes. The building footprint is spread out, so I will need (8) standpipes to cover the hose lay inside the building (fully sprinklered). I'm assuming one 1,000 gpm pump will cover all the standpipe demand.

To complicate matters, this is in a seismic area D classification, and with it being a high rise, I am required to have a secondary on-site water supply. The intent was to install an underground tank to supply the fire pump or pumps, if necessary.

My thought was to supply water directly from the city main to the tank, and if there is ever a break in the city supply line, the pump would be served from water in the tank, which would have enough capacity to serve the facility for 30 minutes.

Is 30 minutes the duration I need?

What do you think about how I plan to serve the building
? Would that meet the requirement for a secondary water supply?

Do I consider the standpipe demand when sizing the underground tank, or just the most demanding area of my sprinklers?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments
Dan Wilder
8/1/2024 09:02:23 am

The secondary water supply will need to be able to meet the sprinkler demand + hose stream per 914.3.2...it does not state the need to be sized to meet standpipe demands....this would also correspond to the duration (based on hazard classification). With the OH areas of the restaurants on the upper floor, this may trigger the 60 minute duration vs the 30 min.

As he building is below 420', 2 separate water supply connection requirements are not in effect.

The primary water supply and duration (sprinkler, standpipe, fire pump) will need to be able to meet full standpipe or sprinkler required floor and pressures (this looks to be several calcs per your description of "spread out") but will likely need to follow NFPA 14-19' 7.10.1.2.1.1 and 7.10.1.2.3.1 (these stick out to me) for the standpipes and also looking at the OH restaurant areas on the top floor.

Some previous discussion
https://www.meyerfire.com/daily/required-duration-for-secondary-water-supply


Reply
Anthony
8/1/2024 09:44:44 am

Dan, IBC 403.3.3 does require a secondary supply as this building is in a class D seismic design category. the 420'-0 designation is only referenced in 403.3.1 and 403.3.2.

Otherwise, I agree with your comments.

Reply
Dan Wilder
8/1/2024 11:39:29 am

Yes, I was referring to the 2 water main connections on different streets for 403.3.2, 403.3 is just a secondary water onsite water supply (i.e. the tank).

Following this conversation
https://www.meyerfire.com/daily/does-tank-meet-secondary-supply-in-ibc

Jack G
8/2/2024 11:31:21 am

914.3.2 Secondary water Supply:
An automatic secondary " on site" water supply having a capacity of not less than the hydraulically calculated sprinkler demand plus hose streams for seismic categories " C-D- E-F ". ( in this case sized for OrdH- 1 or 2, plus hose s for 60 minutes) ad their the design includes mech rooms, maybe retail, and commercial kitchens etc..
The secondary supply shall be on site and thus would preclude an addional connection to the munucipal water supply. SOME municipalities have an exception and will allow a connection to a water main from another municipal main and/ or supplied from another municipal zone. ( philadelphia being one).
An additional fire pump shall not be required, unless the secondary supply cannot deliver the minimum intake pressure to the primary pump.
This would require the primary pump to be sized to supply the building with the " street pressure and boost alone" included in the design of the primary pump, and would over pressure the design when connected to the primary munucipal supply. Additional PRVs would/may be required for hose valves and sprinkler supplys to the floor. The total cost could be huge if a lot of hose and sprinkler valves are in the over pressurized zones.
" the secondary supply shall be automatic"( as opposed to manual).
Generally the intent is a Secondary pump would be required if the secondary supply cannot deliver the necessary pressure to the intake side of the primary pump.
So.....could the Ord Haz areas on the low floors be designed without the pump ?. Talk to the AHJ.
The rest of the building/ floors / standpipe with the primary fire pump? ( AHJ)
The secondary supply sized for light hazard? ( size of tank ) and the street pressure and / or built into the fire pump?( AHJ)
A second municipal supply pressurizing the tank ?
Like a break tank that would supply the tank with additional gpm to meet OH demand.
I m thinking " not" .
The tank should be sized for OH, and the primary pump over sized to include the street pressure and the OH design.
The pump '( if horizontal and not vertical) should be provided with 3-5 feet of head, 'to allow it to wotk properly) meaning the tank bottom being above the suction of the pump. ( otherwise a vertical fire pump.required ).

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top May '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT