I have a CMDA wet system, protecting solid-piled Group A Plastics storage. The storage height will be under 12 feet.
Under Section 21.3.3(a), I have been led to the density of 0.60 gpm/sqft in Column C, over a remote area of 2,500 sqft. The 2,500 sqft remote area is what's getting me; it seems cut and dry that in my situation, I am stuck there unless I have a closed storage array. I wanted to verify against other people's interpretations: are there any other ways I am missing that would allow the area to be brought down to 2,000 sqft? I primarily ask because I have seen other systems in the field with areas of 2,000 with densities 0.40, 0.50, 0.60, and I'm unsure of how those systems have gotten to that point with the current codes. For clarity, I am using the 2022 edition of NFPA 13. Any input would be appreciated. Thanks. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Pete H
8/4/2026 06:15:35 am
From the 2019 edition (you may have to update some reference numbers for 2022):
Reply
Brett
8/4/2026 08:28:22 am
Those references from chapter 19 do not apply to OP's situation since their storage is not classified as an EH1 or EH2 hazard. Section 21.3.3.1 says that the area can only be reduced where either:
Reply
Anonymous
8/4/2026 10:24:38 am
I interpreted 21.3.5 as referring to sprinkler spacing criteria, specifically Table 10.2.4.2.1(c), as 10.2.4.2.1(d) is spacing criteria for High-Piled Storage, which Chapter 3 defines as storage >12ft in height.
Reply
Dan Wilder
8/4/2026 07:57:13 am
Hasn't changed in the 2022 but there are now 2 separate sections to clarify that either condition allows the reduction
Reply
Franck
8/4/2026 11:16:21 am
Reply
Jack G
8/4/2026 12:41:54 pm
Start with the hazard classification curve and take all the reductions like qr heads.
Reply
Jack G
8/4/2026 12:44:58 pm
You should check the MeyerFire cheat sheet for area reduction from I think May of 2022 or so. That may help also
Reply
Anonymous
8/4/2026 01:00:05 pm
I have looked at the cheat sheet, the only note it has about remote area minimums for storage is to look at NFPA 13 for if High Temperature sprinklers may make a difference, on note 4 on the right. Leave a Reply. |