How to Address Water Hammer with Fire Pump?

11/2/2026

14 Comments

 
Does anyone know if there's a way to determine the water hammer created when a Fire Pump turns on (Hard Start)?

I have an existing facility that's about 60 years old with a lot of buried fire mains serving about 10-15 systems. They are on city water at about 55 psi static, and they want us to install a Diesel Fire Pump. Everything in the facility is Ordinary Hazard Group 2, with no plans to add on or change occupancy down the road.

I've chosen a 1,500 gm diesel fire pump at 49 psi, but the owner is worried about blowing out the underground when the pump kicks on. The churn is 55 psi + the city at static 55 psi + 21% for pump overspeed gives us a maximum of around 133 psi that the pump could ever produce.
Although it's not required, we plan to install a main discharge relief valve. Adding 10 psi more for the jockey pump, we could be up around 143 psi, and the owner is not comfortable with this.

What are some options?

Reduce the pump down to 1,000 GPM, 750 GPM?

Reduce the pump's rated pressure to 35 PSI?

​We would need to adjust the PRV's to relieve at predetermined pressures.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
14 Comments
David Kendrick
11/2/2026 08:15:57 am

Verify the existing underground.
Under supervision isolate the supply from the underground and observe for drops in pressure.
Hydrostatic testing of the existing underground and if found to have leakage you can calculate the leakage rate.
Best to know the condition of the underground before it’s necessary in an emergency and found deficient.
There’s a plethora of talent reading this thread that could offer how to control the pumps such that pressure is brought up consistently and gradually to minimize surge pressure’s impact.
Test existing th know what you have before the upgrade.
Personal opinion.

Reply
William Heuberger
11/9/2026 08:15:38 am

Water hammer occurs when a quick closing valve is closed too fast. High pressure does not cause water hammer, but can be a contributing factor to water hammer if the flow suddenly stops.

Reply
Glenn Berger
11/2/2026 08:18:54 am

A few questions first:

Is the underground piping looped?

Are thrust blocks installed?

Material(s) and age of existing piping?

You can run some tests with temp pumps to see what happens.

Reply
Glenn Berger
11/2/2026 10:01:20 am

Another potential solution is to add in a hydro-pneumatic surge tank.

Reply
Jack G
11/2/2026 11:20:50 am

I would use a flat curve pump along with a pump surge suppressor. The pressure I would use is so there is no more than 100 psi on the mains.
First check thrust blocks, then if all of the flange and spigot pieces are rodded thru the floor properly .
Then hydro just the mains and see if the leakage is greater than what’s allowed.

Reply
Helena Vrettou
11/2/2026 12:50:53 pm

What would I recommend?
I would approach the problem in the following order.
A. Establish the actual pressure rating of the existing underground network.
This is probably the most important preliminary investigation.
A 60-year-old underground network serving 10–15 systems deserves particular attention. We need to know:
• Original pipe material and pressure class.
• Whether the network has undergone repairs or replacements.
• The condition of joints and fittings.
• Whether different sections have different pressure ratings.
• The actual maximum allowable working pressure of the weakest component.
The nominal pressure rating of the original pipe alone is not sufficient evidence of its present condition.
B. Obtain the certified fire pump curve.
For the 1,500 gpm pump, I would request:
• Rated pressure at 100% flow.
• Churn pressure (zero flow).
• Pressure at 150% rated flow.
• Pressure at 110% rated engine speed.
Then calculate the maximum steady-state pressure, including the maximum available suction pressure.
C. Commission a transient hydraulic analysis.
I would not attempt to solve this problem by arbitrarily reducing the pump capacity.
The consultant should model at least:
• Diesel pump start-up and acceleration.
• Pump discharge check-valve operation.
• Initial system pressure.
• Different operating demands across the network.
• The pressure surge at the most vulnerable locations.
The analysis should establish both maximum and minimum transient pressures. Negative pressure or excessive pressure reduction can be just as important as positive surge.
D. Consider surge mitigation if the analysis demonstrates that it is necessary.
Depending on the results, possible measures include:
• Appropriate non-slam or controlled-closing check valves.
• Surge vessels or hydropneumatic accumulators.
• Other engineered surge-control devices.
• Modifications to the pump discharge arrangement, where permitted by NFPA 20.
The choice must follow the transient analysis. A device that reduces positive pressure in one location can create an undesirable pressure response elsewhere.
What about the main pressure relief valve?
Here I would distinguish two completely different functions.
• Main pressure relief valve: protects against excessive steady-state discharge pressure, particularly in the diesel overspeed condition addressed by NFPA 20.
• Surge protection: controls transient pressure waves generated by rapid changes in flow velocity.
A conventional main pressure relief valve should not be assumed to provide adequate protection against water hammer. Its opening characteristics, capacity and response time would have to be evaluated as part of the transient study.
I would also be cautious about adjusting PRVs to predetermined pressures simply to compensate for an oversized pump. NFPA 20 does not intend the main relief valve to be used as a routine pressure-regulating device.
Studylib+2
Should they reduce the pump to 1,000 or 750 gpm, or reduce its pressure to 35 psi?
My answer would be: not before establishing the actual hydraulic demand.
The pump capacity must be determined by the required flow and pressure of the most demanding fire protection system, considering the water supply. The fact that the building is Ordinary Hazard Group 2 does not, by itself, establish the required pump capacity.
Reducing the rated pressure from 49 to 35 psi might be possible if the hydraulic calculations support it. But reducing the pump pressure simply to protect old underground piping could leave the fire protection systems inadequately supplied.
Likewise, reducing the capacity from 1,500 to 1,000 or 750 gpm is not a hydraulic surge-control solution in itself.
My conclusion
I think the owner is asking the right question, but the real question is:
What is the maximum transient pressure that the existing underground network will experience when the diesel fire pump starts, and can the existing piping withstand it?
That requires a transient analysis, not simply a fire pump selection calculation.
If I were responding to the original discussion, I would put particular emphasis on the following:
Before reducing the fire pump capacity or rated pressure, I would recommend carrying out a hydraulic transient analysis of the existing underground fire protection network. The analysis should consider the diesel engine acceleration characteristics, pump inertia, discharge check-valve behaviour, pipe characteristics and the configuration of the connected systems.
The maximum steady-state pressure calculated in accordance with NFPA 20 should be evaluated separately from the transient pressure surge. A main pressure relief valve intended to address diesel engine overspeed should not be considered a substitute for appropriate surge protection.
Given the age and extent of the existing underground network, I would consider the transient analysis essential before

Reply
Colin Lusher
11/2/2026 02:51:58 pm

Please don't ruin this forum with ChatGPT responses. We can all do that at home. We come here for real, thoughtful responses from real people. This response has all the hallmarks of AI, but if I'm wrong, my apologies.

Reply
Ed Glynn
11/2/2026 02:21:35 pm

My question starts with the systems are on existing city pressure at 55 PSI. What are the calcs for the existing sprinkler systems ad why at this point in time are the owners wanting to add a diesel fire pump.

How did you derive your pump sizing calcs to determine that a diesel fire pump rated at 1500 GPM and 49 PSI was appropriate?

I would start with the required pressure and flow for the largest fire sprinkler system and work forward from there.

Reply
Helena
11/2/2026 02:50:57 pm

Actually, I think we try to solve a problem from the end of the story.
In my opinion, there are two separate engineering questions here, and they are being mixed together:
1. Why is a diesel fire pump needed at all, when the existing sprinkler systems operate on city pressure of 55 psi?
2. How was the proposed pump duty of 1,500 GPM at 49 PSI established?

I would actually challenge the proposed pump sizing before attempting to calculate the water hammer.
Where did the 1,500 GPM come from? Where did the 49 PSI come from?
Were these values derived from hydraulic calculations, or was a pump selected first and the calculations subsequently adapted to it?
That is a fundamental distinction.
And one last observation: if the existing systems have been operating satisfactorily on city pressure for decades, I would be very interested to understand what has changed to make a diesel fire pump necessary now.
I would not start designing around an unexplained pump duty point.
We need the hydraulic justification first. Then we can investigate the transient effects of introducing the pump into the existing network.

Reply
Helena Vrettou
11/2/2026 02:53:27 pm

And I think the most interesting part is that the water hammer may not be the first problem to solve.
Before worrying about the pressure surge, we should establish whether the pump is actually necessary, whether its duty point is justified, and how it will interact with the existing network.

Reply
Mark Harris
11/2/2026 05:14:16 pm

Lots of extensive discussion so will keep it brief. First as several have questioned why a pump now if systems were designed on 55 PSI city pressure. Totally agree with that question. Second where is the sizing coming from? Are there private hydrants and sprinkler systems or just sprinkler systems?

If owner concern is reliable water supply a pump supplied from a private ground storage tank may make more sense (and more money).

If it is determined that the pump is necessary or desirable the integrity of the underground pipe is paramount. There are already comments in the blog on that process. Existing materials should have minimum 150 PSI rating. As far as a pump rating unless something changed the minimum rated pressure is NFPA 20 is 40 PSI.

I have seen this done (pump added to old underground) without checking the integrity of the existing underground and then the jockey pump jockey pump never stops (leaks exceeded capacity of jockey pump). Owner needs to be warned doing this work could also end up requiring the replacement of all or at least portions of existing underground.

Reply
Nimal Tissa Wijetunga
11/2/2026 10:37:26 pm

1)In my view, to settle the water hammer issue,you need to maintain maximum Velocity as 15 feet per second in all segment of the pipe network.
2)It is always advisable to have electric jokcey and diesel operated as fire pump set in Fire systems.
3) complete hydraulic calculations to understand pump rated capacity,rated head and appropriate pipe sizing in the system.

Reply
Streeter
11/3/2026 09:23:49 am

Not something that addresses the water hammer, as much as the fact that life safety systems need to be functional and work as designed. I would determine the fire pump size first off of the most demanding remote area and then subsequently address the water hammer issues where they might occur.

Reducing the pump size is fine if it still allows the systems to operate as intended but if that's the case, why not size the pump to that size in the first place?

Reply
M.A
11/4/2026 07:30:38 am

From my point of view,

Since you are questioning the pump flow rate, I think the first step is to review your hydraulic calculations and confirm the actual required flow and pressure.

A pressure relief valve can be used as per NFPA 20:2019 to limit excessive system pressure. However, it is not necessarily a solution for water hammer.

Considering the age of the existing network, a surge analysis may be required. Although pressure spikes can occur during pump startup, the more severe spikes are often caused by sudden pump shutdown, rapid valve closure, or check valve slam.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 221
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 88A
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    November 2026
    October 2026
    September 2026
    August 2026
    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT