|
We have a disagreement on a fire pump installation. Flow test shows 42 psi static, 10 psi residual at 475 gpm from an 8" municipal main.
The fire sprinkler contractor plotted the water supply curve and says it cannot support the specified 1,000 gpm @ 100 psi pump; they're refusing to certify the fire pump without a suction tank or another resolution. The mechanical engineer argues the 8" main at 42 psi static should theoretically deliver way more than 1,000 gpm and questions whether the flow test results accurately represent what the pump will actually see at its suction connection. The steep pressure drop (42 psi to 10 psi in only 475 gpm) seems abnormal for an 8" main. The area has aging infrastructure and known low-pressure issues. Looking for the community's input on: (1) Is the fire sprinkler contractor correct to base their analysis on residual pressure under flow conditions, or should we be looking at static pressure as the mechanical engineer suggests? (2) What's the correct NFPA 20 methodology for evaluating water supply adequacy for a fire pump? (3) When you see such a steep pressure drop in a flow test, what are the typical causes and how would you approach resolving this? What solutions have worked for others dealing with marginal municipal water supplies? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
17 Comments
1/20/2026 08:14:53 am
1. There is a serious problem with the public water supply. Either an obstruction in the lines or a partially-closed valve.
Reply
NK
1/20/2026 08:19:07 am
Yikes.
Reply
NK
1/20/2026 08:25:29 am
These are the correct sections:
Reply
Jonathan Griffin
1/20/2026 08:19:09 am
The water flow test that you describe has real issues: the Minimum flow required for firefighter use is based upon a 20-PSI residual pressure, and usually more than 1,000 GPM.
Reply
Art G
1/20/2026 08:19:59 am
To see that much of a drop in an 8" main would be very rare but possible.
Reply
D
1/20/2026 08:20:01 am
Firstly, static pressure alone does almost nothing for us here. If the city has booster pumps we may see static pressure of 42 psi and a drop in residual pressure that is barely noticeable without opening many hydrants to as nfpa 291 suggests. Residual pressure and flow is the way that we are able to plot a supply curve- static pressure only is not going to help us diagnose this issue.
Reply
D
1/20/2026 08:23:12 am
Also want to add (just for fun) that it's scary the engineer says static is all that matters. As others have said, 'yikes'!
Reply
Derrick
1/20/2026 08:23:40 am
Unless you have another flow test that shows different...you have to have a pump and tank. If it only delivers 485 gpm @ 10 psi. It would never be able to deliver 1,000 gpm at a positive pressure to your building without additional capacity. I don't see how you can base the flow on static pressure only.
Reply
Glenn Berger
1/20/2026 08:26:21 am
Lots of questions presented -
Reply
Anthony
1/20/2026 08:33:45 am
How to Address Fire Pump with Poor Supply? -- with money.
Reply
1/20/2026 08:39:31 am
Not to step on toes, but using a static pressure to determine water supply is wrong for fire protection, your contractor is correct in their efforts. Works great with plumbing fixtures...has no place in fire protection at the contractor level (IMO) specifically for this reason.
Reply
Stephen P Merrill
1/21/2026 11:28:58 am
Always- Always require a hydraulic gradient to be done prior to suggesting a pump or it size. The must be done in recently not results for 3 years ago.
Reply
Dave Branson
1/20/2026 08:53:27 am
I have a similar situation on a private campus, with my flow test yielding 44 psig static, 27 psig residual and 650 gpm (15 psig) flowing. My remote load plus hose allowance is approx. 800 gpm for 90 minutes. I'm looking at a 91 kgal water storage tank and a 1,000 gpm fire pump to handle the remote load. The existing main should have enough pressure to refill the tank within 8 hours.
Reply
Jack G
1/20/2026 09:04:53 am
I think the water supply should be evaluated by performing other flow tests to determine if there really is an obstruction in the incoming line to the fire pump.
Reply
Dwight Havens
1/20/2026 12:19:34 pm
Good discussion. The available water supply needs to be fully evaluated and it's configuration understood. I have seen sprinkler systems designed to the available flow from the two nearest hydrants, only to find that the 6-inch main that completed the the top of the grid between the two hydrants was corroded to less than 3-inches in diameter. Problem was found during acceptance testing using the Main Drain for flow. In other words, the assumptions made from the flow test and the piping connecting the two hydrants did not reflect the realty of the reduction in diameter of the 6-inch main to which the system was initially connected. Of course, in this case, the reality of the main configuration was unknown until the investigation into the cause of the poor Main Drain test reveled it.
Reply
Ed Kramer
1/21/2026 10:24:33 am
Great questions and discussion.
Reply
Jose Antonio Garcia
1/21/2026 11:09:26 am
I believe the key element that hasn’t been mentioned in the comments is this: What is the actual demand of the sprinkler system?
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Dec '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
February 2026
PE PREP SERIES |
RSS Feed
