When conducting main drain test on a sprinkler system with a fire pump, should the pump be on or off?
AHJ generally wants the pump to be on in this area. Thanks. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Dan Wilder
5/24/2024 07:51:27 am
The test should be done at the main drain closest to the supply/source with the pump off. NFPA 25 says "for each water supply lead-in". It would be near impossible to decern a water supply degradation instead of a pump degradation, or a combination of both, with the pump running based only on a main drain test.
Reply
Glenn Berger
5/24/2024 08:15:32 am
Depends -
Reply
Derek G.
5/24/2024 08:34:52 am
Agree with Dan here. It should be off, but as an AHJ and former fitter, I would also capture the numbers with it on.....it doesn't hurt to have both sets of values.
Reply
Jack G
5/24/2024 09:16:28 am
The fire pump should be off.
Reply
Franck
5/24/2024 09:18:28 am
If you are talking about the 2 in. drain test, it should be done with the pump on.
Reply
Franck
5/24/2024 09:21:38 am
By "on", I mean "pump in automatic mode". But the pump is not running when you start the 2" drain test. You start the pump by pulling down the pressure in the system.
Reply
Steve Cooper
5/24/2024 09:41:00 am
With the fire pump off, would make sense per code, but your AHJ could just want extra values and tests. Many AHJs we work with like to ask for much more than NFPA requires.
Reply
Matthew Mueller
5/28/2024 07:45:41 am
This was something that was taught to me early on and was a significant change to how my company, and most companies in our area had been doing this test. The fire pump is an integral part of the designed water supply. In addition, all tests required by NFPA 25 are required to be performed with the fire pump in "on" (automatic) unless impairment procedures are followed.
Reply
Jay
5/29/2024 03:45:40 pm
I agree with #2.....there is no need to do a main drain test on a system with a fire pump because the suction pressures from the annual pump tests can be compared to identify a reduced water supply
Reply
Matt G
8/15/2024 04:35:28 pm
That is not entirely correct Jay. Facilities that have fire pumps in stand alone pump houses that feed underground piping that supply the sprinkler risers in the main building(s) certainly need main drain tests completed. This is to ensure no isolation valves are shut / partially shut or major deterioration / blockage of the underground supply piping. Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Feb '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
March 2025
PE PREP SERIES |