Can ESFR sprinklers be used in a manufacturing building that is 63'-0" high to protect an Ordinary Group 2 occupancy?
NFPA 13 2022 14.2.7 allows the use of ESFR to cover OH2 and lower occupancies, but I believe that those occupancies are located in storage areas or are incidental to the storage being protected. FMDS 3-26 and 8-9 allow their use up to 100 ft, but they do not classify ESFR sprinklers the same as NFPA. Any thoughts? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Pete H
5/21/2026 06:33:22 am
I think I'd say no.
Reply
Dan Wilder
5/21/2026 07:31:39 am
In no particular order...all referencing the 2025 Edition
Reply
Glenn Berger
5/21/2026 08:28:22 am
In addition to other responses - Check the manufacturer data sheet. You probably will not find many sprinklers approved for heights above 55 feet.
Reply
Robert
5/21/2026 09:21:38 am
Reach out to the manufacture to clarify maximum height for the sprinkler head and request a document, if possible, for AHJ. if the design method used does not specify a maximum height the guidance to follow would be manufacture spec.
Reply
anthony
5/22/2026 08:34:20 am
Short answer no. There are no ESFR sprinklers (that I know of) that are listed for over 55ft ceiling levels. others have mentioned that ESFR can protect OH2 but you run into the limitations of what an ESFR system can do.
Reply