I am working with a company storing Class IIIB liquids in plastic tanks. Tanks range in size from 2000, 3000, to 6100 gallons.
We struggled to find a design that works in NFPA and therefore went with a .40/3,000 from FM DS 7-32; however, now we do not know what to do with the containment requirements. What should the containment duration be? Since they are plastic tanks, I have assumed they would all fail and would essentially need containment around each tank? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments
Jesse
7/27/2026 08:25:49 am
I think you're asking about duration of sprinkler discharge as it impacts the secondary containment, so I'm guessing this is indoors and rain isn't a factor.
Reply
Anthony
7/27/2026 09:22:01 am
I'll unhelpfully add here that NFPA 30 runs you in circles for interior tank storage. Very difficult to VE anything here with out oodles of experience.
Reply
Felipe
7/27/2026 10:39:04 am
You can reference IFC Section 5004 - Storage
Reply
Dan
7/28/2026 01:35:14 am
FM 7-29, InterimRevisionApril2026, Table 2.2.2.1.B. Drainage and Containment Requirements for Liquid Storage in Plastic, Glass or Other Combustible Containers in Cutoff Rooms/Buildings (continued):
Reply