If a duct detector is installed, and the mechanical unit has a capacity of less than 2,000 CFM, it is required by code for the duct detector to be connected to the fire alarm panel?
Alternatively, removing the detectors can be considered in this situation. Looking for relevant code and standard basis. We're under the 2021 IFC, 2021 IBC, and 2019 NFPA 72. Thank you! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Glenn Berger
3/7/2025 08:10:30 am
NFPA 90A (2021) Section 6.4.4.2 requires the connection to the building's fire alarm system if one is installed.
Reply
Glenn Berger
3/7/2025 08:12:07 am
One more item - If this was my project, I would still connect all smoke detectors that are installed to the building's fire alarm control panel.
Reply
Robert Kessenich
3/7/2025 10:27:45 am
Glenn, I agree with you. If it is installed it should have an acceptance test, operate and signal the same as those that are required.
Sean H
3/7/2025 08:15:11 am
Notably, NFPA 90A is not a referenced standard in the IBC, so you'd be under the purview of the IMC as modified by any locally adopted amendments. If you don't meet the CFM threshold, the unit likely does not require a duct detector. It can still be a bit of a gray area in the eyes of an AHJ if a building is equipped with certain safety features and you want to remove/lessen the amount of safety - it's a good talk with the AHJ to make sure all parties are on board before doing so though.
Reply
Todd E Wyatt
3/7/2025 08:16:41 am
The scoping Code (IBC-2021) determines where "duct smoke detectors" (DSD) are located per 907.2.13.1.2.
Reply
Todd E Wyatt
3/7/2025 08:24:26 am
The reference to 907.3.1 from 907.2.13.1.2 above :
Reply
Darin
3/7/2025 09:54:07 am
Respectfully disagree. Duct detectors are required in many commercial and residential buildings that are not high rise. The scoping code in most jurisdictions related to any hvac requirements is the mechanical code(most jurisdictions adopt the IMC or UMC). Air moving systems that produce is excess of 2000cfm require a shutoff upon detection of smoke via a duct detector or one of the exceptions is via area smoke detection. The only real difference between the UMC and IMC is the duct detector location (UMC requires it on the supply side and the IMC on the return).
Reply
Christopher Nelson
3/7/2025 10:09:45 am
I have been told a lot of hvac units have them installed already from the manufacturer and they have to get ripped out for fire alarm duct detectors to be installed. I wonder if this is one of those instances.
Conrad
3/7/2025 11:34:29 am
During fire alarm acceptance testing in our (NFPA) jurisdiction, if duct detectors are installed. If there are voluntarily installed duct detectors, they need to be connected to the fire alarm system.
Reply
Keith.O
3/12/2025 10:26:08 am
Another interesting dilemma I often come across between the IMC/UMC and NFPA 90A and NFPA 72 is the issue of where and how many duct detectors are to be installed.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Feb '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
March 2025
PE PREP SERIES |