Double PRV Arrangement for 9-Story Building?

10/14/2026

8 Comments

 
I have a 9-story residential building with 3 levels of parking. The building requires a fire pump. The AHJ limits us to a design pressure of 60 psi regardless of the available water pressure.

In my case, the available pressure is 85 psi static, and I have a 115 psi fire pump with a 134 psi shutoff pressure. Therefore, I need to reduce the pressure to ensure that the system does not exceed 175 psi.

I am planning a double pressure reduction, with the first reducing valve set at 162 psi and the second reducing valve set at 165 psi, with the second valve essentially acting as friction loss only.

Assuming a 5 psi pressure increase per floor, would it be acceptable to supply two basement levels below the pressure-reducing valves and reach 172 psi at those levels?

I have already noticed that PRVs can have up to 10 psi above their set point under static conditions, which would make the pressure exceed the maximum limit of 175 psi. To eliminate this overshoot, I plan to install a 1-inch pressure relief valve set at 165 psi to ensure that the system pressure never exceeds 175 psi. This solution seems ideal, except in the event that the pressure-reducing valve is unable to stabilize the downstream pressure below 165 psi. In that case, both the pressure-reducing valve and the relief valve would remain slightly open, allowing a continuous flow of water. This could cause the jockey pump to start repeatedly in an attempt to maintain system pressure, potentially resulting in premature wear of the pump.

Do you have any advice to help me in my design?

​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Brett
10/14/2026 10:22:32 am

I recommend reviewing the manufacturer cutsheets for the pressure regulating valves closely and contacting them if you still have questions. All the master pressure regulating valves I've looked at recently require minimum 10-20 psi drop across the valve. Also consider the minimum flow rate through the valves and whether it can handle the low flow of one sprinkler flowing water.

The relief valve you mention is required by both NFPA 13 (2019 - 16.9.8.3) and NFPA 14 (2019 - 7.2.4 (8)). NFPA 13 requires a minimum 1/2" relief valve but NFPA 14 says to provide it in accordance with the pressure regulating valve manufacturer's instructions. The pressure regulating valve manufacturer might require a larger relief valve than 1/2".

Reply
Paul Pinigis link
10/14/2026 10:43:43 am

First, you have to find out why the AHJ has a 60 psi design pressure. One the surface, this seems completely illogical.

Reply
Dan Wilder
10/14/2026 02:11:18 pm

I've got one that only allow 45PSI....maximum static.

I am not looking forward to any of the upcoming OH design increases for roof height with that stipulation.

Reply
Dan Wilder
10/14/2026 02:36:02 pm

Any of the larger PRV (pilot operated) will also require a low flow bypass and the UL listing limits them to 165PSI along with the minimum loss across the valve once the residual pressure lowers the pressure enough for that to become a factor.

Not sure about the thought process behind 2 valves? Friction loss needs a flow...in a static condition, it seems you would exceed your maximum. Is this a parallel setup or series?

If both valves are open relieving pressure, your fire pump is likely to turn on.

A 175 PSI relief valve will start discharging at well below 175PSI and even lower to reset itself. AGF has a great write at the bottom of their valves about this. Relief valves should already be open by the time they reach their set pressure, that is a maximum setting.

I have a 10 story + 2 below ground that I can make work with a fire pump set to 170 at churn (with the city supply). Now this is a 750 GPM standpipe design so it's not a large building. As to thoughts, you could split the system to be fed from the city for the lower floors and the fire pump for the upper (this triggers some creative thinking for FDC tie-ins, signage, bypass options). If that isn't going to work, we have used 300 PSI sprinklers for the lower floors (250 PSI for valves) with a lot of signage. If there isn't anything special about the lower floors, other than a coupling and sprinkler adjustment, verification of the valve ratings, and some other smaller items it may be a cheaper route than a second valve setup.

https://content.agfmfg.com/assets/Uploads/CutSheet-M7000L-7200L-v2.pdf

Reply
Bryan L
10/15/2026 09:26:46 am

Thanks for your answer Dan.

I have 2 reduction valves in series because the reduction supply the entire building. NFPA 14 2014 7.2.4 states that when a reduction supply more than two hose connection, you need a second reducing device.

By setting the first device at 162 psi and the second device at 165psi, I make sure there is not more than 175 psi to the hose connection or the sprinklers. In this set up, the first device always reduces the pressure while the second one always stays full open. The second device only reduces if the first one fails. Claval rep approved this set up.

The issue I face is the static pressure observed after the first reducing valve. Even if it reduces to 162 psi while flowing, the pressure observed in non flowing condition is 7-8 psi more. This would result in too much pressure to both floor below.

Do you take this overpressure in your design?

If yes, I would need to add for example factory set reducing valves on both control zone and factory set valves as hose valve on the floors below.

You seem to say that it is not possible to set the relief valve at 165 psi because it will open before its set point and make the fire pump start. What is the minimum delta pressure between the relief set point and the actual pressure?

Reply
Jack G
10/14/2026 07:45:38 pm

The 60# is curious.
So I m assuming just the Mrs design is limited to 60# residual pressure.
The standpipes will still require 100# at the top per NFPA 14.
The churn is 134# plus 85 # which adds up to 219 psi on the duscharge side of the fire pump.
The standpipes will require 100# plus 45 # elevation loss and add the friction loss from pump to top , plus BFP LOSS plus underground loss to the test hydrant.
IF Standpipes are 500 + 250, with 6 inch supply ( 12 psi approx loss) or 4 inch supply ( 26 psi loss approx) 6 psi for BFP, 5 psi underground loss , you will need at least 163 psi and a 10 psi safety prints the requirement pressure at 173#.
So if STANDPIPES require 173, a pump discharge side prv would not work.
So the standpipe valves will require ( some) Adjustable fire hose valves ( FHV) . The floors will require Adjustable prv - floor control valves. The floor ( all including the lower floors) valves should be set 10 psi below the maximum static pressure for the reading at each floor. ( for relief )
Grooved couplings and fittings can be rated for up to 300# along with the valves and floor checks , 250 or 300#)
The fire marshal is requiring the residual design pressure not to exceed 60 psi.
The curve floor static , prv residual at the floor calculated flow .

My problem with safety factors is that if you did a DEMAND CALC that works to that design scenario (60#): and then did a supply calc ( which is what scenario a fire would do ) ( valves are dumb);
the supply calc ( opening up the same remote area— and these floors will have huge safety factors) , the supply calc will show that the design will overflow the water supply.
( I use the supply calc to tweak pipe sizes to limit overflow)
Try it . Then show the AHJ the outcomes and he probably allow you to do the max design per NFPA 13.

Reply
Jack G
10/14/2026 07:51:41 pm

I also like the idea above of splitting and running a separate sprinkler only riser to the parking floors that would operate unde Streep pressure. Appropriate FDC connection arrangement so that 1 FDC Will supply both.
And I see only using 1 prv. A second one on the pump supply possibly choke the pressure required for the standpipes.

Reply
Nimal Tissa Wijetunga
10/15/2026 05:35:57 am

Considering the system requirement,friction losses and static loss, the best practise is to have two set of Fire pumps and water tanks for basement floor and the higher floors separately in line with fire engineering where maximum pressure to be maintained at or below 175 psi.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 221
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 88A
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    November 2026
    October 2026
    September 2026
    August 2026
    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT