If there are sprinklers installed under the ceiling of the sloped roof, is the combustible concealed space not required to have sprinklers in accordance with 9.2.1.5 (NFPA 13 2019)?
Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Brett
10/8/2026 06:39:06 am
Those spaces appear to be framed out with open web trusses. Section 9.2.1.5 only applies to solid structural members such as 2x10s for example.
Reply
Dan Wilder
10/8/2026 08:18:28 am
As Brett hit the particulars, the below site gives a nice description of the types of spaces along with a visual for reference.
Reply
Sean Andrew Fallows
10/8/2026 10:12:53 am
this is the most complete answer no matter the construction
Reply
Streeter
10/8/2026 09:22:25 am
Brett and Dan kind of handled it but, keep in mind that the allowances of 9.2.1 are very specific to the structure type (open web vs solid wood vs composite wood joist.)
Reply
Joe F
10/8/2026 10:45:40 am
I concur with all reply's above. As Streeter mentioned above, filling the open web trusses with insulation is the best option for the building owner, This will provide a higher R Value for insulation purposes and eleminate the extra layer of fire spinklers withing the joist cavity.