MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Does Max Pressure, Hazard Matter for Deluge?

7/24/2025

12 Comments

 
Does maximum pressure and allowed hazard classification for any sprinkler (such as light hazard, 175 psi) really matter in a deluge system?

I have a design situation where I need to use 8.0K extended coverage sidewalls listed for light hazard use, to achieve an FM Global Hazard Category 2 (HC-2), 0.60 gpm / 1,200 sqft, and I cannot accomplish that without exceeding 175 psi.

Since the heads are open, I would think that pressure and rating do not matter since the activation will be by electronic devices.

​Does it matter?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Pete H
7/24/2025 06:21:36 am

Did you use high pressure fittings? And valves listed for higher pressures as well?

Cause if say the threaded connections from the branch line to the open sprinkler head is only rated for 175 psi, and you have more than that, you will likely impact relevant system performance. The activation may be by electronic devices, but the delivery is still water pressure.

Reply
Brett
7/24/2025 06:52:43 am

Yes, they both matter and you'd be opening yourself up to liability if a component failed or the system didn't operate as intended. As far as the hazard classification goes you might need to work with an FM representative if you can't find a sidewall that's approved for HC-2 occupancies. If their datasheet specifically calls out an extended coverage sidewall for an HC-2 occupancy then the sprinkler must exist.

Reply
Glenn Berger
7/24/2025 08:21:35 am

Maximum pressure always matters. There are fittings, valves, and other components that still need to operate correctly.

Reply
Dan Wilder
7/24/2025 08:28:21 am

NFPA 13-19' 7.1.2 Rated Pressure - Components shall be rated for the maximum system working pressure...

3.3.216 System Working Pressure - The maximum anticipated static (nonflowing) or flowing pressure applied to sprinkler system components exclusive of surge pressures and exclusive of pressure from the fire department connection.

On the surface this would not be allowed.

A call to the MFG on the sprinkler capabilities could occur but I highly doubt anyone will sign off on an untested design pressure.

If the sprinkler was a density/area-based design method on the data sheet this "could" be acceptable assuming the sprinkler was rated for the higher pressure, but for an extended coverage sprinkler there is no data to support the density would be achieved by just using the SxLxDensity to get the needed minimum discharge.

Reply
Louie Lincoln
7/24/2025 08:30:29 am

It may matter even more on a deluge system as when it trips the surge is astounding.

Reply
Chris
7/24/2025 08:35:39 am

Not to de-rail the question, but code literally tells us to exceed the rated pressure of fittings for hydro-static tests. Most hydro's end up having a pressure of easily 220psi, and usually the field will pump it up a day before so that it is ready and settled by the time the actual inspection takes place. If this occurs on a Friday, I have heard that systems will go the weekend over 220psi with threaded fittings rated for 175psi and have no issues.

Code creates a single exception with hydro's where we exceed the 175psi maximum pressure, but it doesn't create any guidance on other exceptions that could take place. There are many times that when designing a fire pump system, the churn will bump a system pressure up above 175psi slightly, and I have had to debate the need of a Master PRV to keep the system below 175psi, even though it would only be >175psi for usually less than an hour.

The issue code seems to be trying to solve is that if a system stayed above 175psi for a year, it would likely create issues with threaded fittings. It would be very helpful if there was an exception for pressure exceeding 175psi for short duration's so that these exceptions can help save contractors from spending more unnecessarily.

If this was the case, this exception would allow the Deluge design listed above to be temporarily above 175psi, it would help lots of fire pump designs, and would make more logical sense as to why we hydro systems at 200psi for 2+ hours.

Reply
Anthony
7/24/2025 08:38:02 am

I'm not sure you should use sprinklers listed for light hazard in an HC-2 category design. FM might reject the design. FM has specific sprinklers/nozzles listings for exposure protection that might be worth a look.

Reply
Franck
7/24/2025 10:00:50 am

There is one big concern with high pressure: the water distribution pattern and the water droplet size.
Sprinklers best operate between 7 psi and 60 psi. Above 60 psi, the water droplet size tends to be non homogeneous and more fine droplets (not able to penetrate a severe fire heat plume) are created.
In addition, the distribution pattern tends to be more elliptical and all areas might not be fully covered.
This is some of the reasons why the spacing for EH commodities are smaller and why we need higher K-factor for storage occupancies when the density is above 0.2 gpm/sq ft.

On top opf that, sidewalls are normally not accepted for hazards that are more than the Light Hazard classification. This is also related to the efficiency of sidewall sprinklers that is not as good as standard spray sprinklers for high densities.

In your case, there are high chances that the AHJ will not accept the design, and the fact that it is a deluge system does not solve the problem.

Reply
David Kendrick
7/24/2025 10:18:23 am

Have you checked the possibility of using smaller orifice heads closer to the mains and riser?
Unless it’s restricted by the standard governing your project balancing a deluge system can be improved when smaller orifices are applied.

Reply
Jack G
7/24/2025 11:17:19 am

Yes it does matter.
First if mailable iron fittings they are permitted by 13 to be used with 200 psi and if new fittings they are probably mal. Iron rated for 250 psi. Grooved should be no problem.
Now hydraulics.
I ve found it’s best “ to allow the sizing and flow thru the pipes” to control the amount of water discharged.
This can be accomplished ( like the old days) for a center- center design——- sprinklers on lines, branches on mains. Center the supply. ( like as an exaggeration— if you had 5000 gpm going in, only the density times the area ( or as close as possible ) is discharged,controlled by the pipe sizes—- no safety factor— as that in itself causes overflow and pressure.
This should cut down on overflow and pressure drastically.
Now for my next “ tool” I perform a “ supply calc” - tweaking the pipe sizes as required to balance the flow/ pressure.
After getting it tweaked, I do a demand calc, and wha-la, the overflow is minimized.
So the design of the system could be causing it not to work.
( calc a normal system with 10 psi safety. Then add the 10 psi to the end head—- calcs overflow when excessive pressure is used)
And the system doesn’t hit the density or flow.

Reply
Kenneth Casey Milhorn
7/25/2025 09:28:51 am

Yes, as Franck said, it's not only about the activation element to "hold back pressure", but it's about the spray pattern. The spray patterns and droplet sizes can change dramatically at higher pressures. Also, many of these sprinklers are listed for 250 psi with the exact same "parts", manufacturing process, etc. it's just the fact that the manufacturers didn't spend the money to have them listed at the higher pressures because it wasn't a good ROI. Most likely, the rest of your components are listed to 250 psi or greater. Many times it does come down to the sprinkler head as the limiting factor for system pressure. Worth a call to the manufacturer to see if they will write a letter, especially if they have some documentation of testing they have performed on this head at higher pressures. You never know unless you ask.

Reply
Phil Watkins
7/25/2025 10:26:22 am

I'd be very surprised if you are going to see 175 psi residual pressure at any of your open sprinklers when the whole system is operating (although not impossible of course depending on total system flow rate and water supply performance).

If you enter your pump performance curve into the calculation you should see the actual pressure and flows.

Although its important not to deliver higher pressures than the nozzles are designed for (overpressure often means deterioration of the water droplet size etc) its often impossible especially where the system has multiple deluge systems of different sizes (water supplies designed for massive systems sometimes feed very small systems),

Quite honestly I've seen probably a hundred different deluge systems operating over the years and running pressure at remote nozzles are usually quite high but overall area water delivery when taken as a whole is more than satisfactory.

Have you considered using directional open nozzles (such as medium velocity) as they have alternative k-factors and spray profiles that might suit your application?

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top July '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    August 2026
    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT