I am attempting to tweak a set of calculations that is slightly over the curve.
When measuring/assigning an area of coverage for an individual sprinkler into a hydraulic calculation program I am told the area per sprinkler is the largest dimension x 2, not the physical area the sprinkler protects. This is because the required distribution of water will be based on the largest dimension regardless of the physical dimensions of area protected. Comparison example: 1) Physical Area for Pendent Sprinkler coverage is 14 x 8 = 112 sqft Flow determined by 112 sq ft x .10 gpm = 11.2 gpm 2) Largest Dimension x 2 determines area per sprinkler and area is 14 x 14 = 196 sqft Flow determined by 196 sq ft x .10 gpm = 19.6 gpm Thanks in advance for your opinion and code basis. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Dan Wilder
2/2/2026 07:52:53 am
Unless your sprinklers are residential, extended coverage, CMSA (sometimes) or ESFR, the SxL method is the correct approach.
Reply
NK
2/2/2026 08:26:44 am
There is nothing in NFPA 13 that limits the square footage used in CMDA hydraulic calculations, however contract documents, AHJ requirements, insurance requirements may dictate maximum allowable spacing be used for future modifications. If you use a smaller area than the maximum, make sure it's clearly indicated on the drawings and calculations, noted on the hydraulic placard/general information sign, and that the spacing throughout the building matches the spacing of the sprinklers in the remote area that you proved hydraulically (you can't calc to 196ft and space 225ft everywhere else without additional calculations).
Reply
DG
2/2/2026 11:20:23 am
Definitely the largest of x2 dimension is what determines the area per sprinkler (so in your comparison example the coverage area is 196sqft not 112sq ft). I won't repeat good points already stated; however wanted to add one. If you have a OH occupancy, based upon the example you gave, you would end up with two heads in that small compartment vs one as the coverage area exceeds 130sqft.
Reply
Wes
2/2/2026 11:40:48 am
DG, in your 14 x 8 example, where does this requirement originate?
Reply
Brett
2/2/2026 02:19:08 pm
Wes, the general spacing rules are in section 9.5.2.1 in the 2019 edition of NFPA 13. Dan pointed out the other applicable sections above (although there is a typo - 27.4.2.6.2 should be 27.2.4.6.2) and the fact that some sprinkler types have different spacing rules that override 9.5.2.1. Leave a Reply. |