MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Control Valve Allowed Directly Below Hydrant?

6/27/2025

10 Comments

 
Is the installation form of the control valve for the hydrant correct/allowed as shown?

It is a wet barrel hydrant, and the owner wants to save costs by installing the control valve directly below the hydrant.

​How should the effective coverage area of the fire hydrant be considered?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
10 Comments
Pete H
6/27/2025 06:37:47 am

From NFPA 24 (2025 Edition) Chapter 7: Hydrants

7.1.1.2 A listed control valve shall be installed in each hydrant connection.
7.1.1.2.1. A valve required by 7.1.1.2 shall be permitted to be a listed, nonindicating valve, such as an underground gate valve in a roadway box.
7.1.1.2.2 Valves required by 7.1.1.2 shall be installed within 20 ft. of the fire hydrant.
7.1.1.2.2.1 Valves shall be clearly identified and kept free of obstructions.
7.1.1.2.3 Where valves cannot be located in accordance with 7.1.1.2.2 valve locations shall be permitted where approved by the AHJ.

I can find no requirement about the control valve needing to be underground as is the normal installation, though I would worry if you can find one that can be installed above ground that is listed for such purpose the same way a curb box valve would be. But it's definitely within 20'-0". Ultimately, given 7.1.1.2.2, I'd advise if you're doing any installation with a valve location "outside of the norm" even if you can't find a code prohibition, get the location approved by the AHJ.

Take with a grain of salt, I'm not looking at this harder than NFPA 24 right now.

Reply
CESAR LIRA
6/27/2025 02:21:43 pm

This can't do it. because the hydrant has a own gate in the elbow,. if there a different hydrant the gate valve could be a problem for the walkers

Reply
Dan Wilder
6/27/2025 08:12:44 am

I would argue "Not Allowed" as this creates an obstruction to the operation of the hydrant for a responding crew for 360° clear access.

I would also venture this violates ADA requirements if located anywhere on a public sidewalk or pedestrian path.

Reply
Chad
6/27/2025 08:48:47 am

Agreed-

Plus, if a car hits that, the valve is toast and you will have to shut down that whole main to fix….. water agency might not like this.

Reply
Anthony
6/27/2025 09:45:30 am

I agree with Dan and Chad here about the creation of an obstruction and a car problem. It just looks like it creates more problems than it solves.

Reply
Glenn Berger
6/27/2025 08:14:42 am

For a WET BARREL Fire Hydrant this appears to be legit from an NFPA standpoint. Might want to check the applicable OSHA requirements. If no guard posts are present on all sides as the Gate Valve will be a protruding item at a low elevation.

Effective coverage area of the hydrant will not be affected with providing an aboveground isolation valve.

Reply
Jack G
6/27/2025 12:18:30 pm

The hydrant may not work properly work mounted directly to the bottom of a hydrant . The stem of the hydrant moves up and down to open and close. When closed it moves past the weep holes that allow drainage of the hydrant. This feature may not work.
The hydrant control valve is an underground valve and is referred to as a “ hydrant repair valve “.
I m assuming the climate “ never freezes there” as the os&y “ is above grade and that regression is “ no frost line. “.
The hydrants usually come with the elbow for the stem “ open and close “ already attached.
I d check the UL listing of that hydrant as it may not be listed for your configuration.
In 57 years as a fire protection contractor , I’ve never seen or installed this way.
I d never do this as it just seems inappropriate .
Wall hydrants ( above ground on a building wall) fed from inside the building at the riser ( across to the opposite wall ) to avoid underground pipe installation) have a “ wall post indicator attached to a listed wall hydrant) are usually installed to avoid underground pipe behind the building.
The cost of a wall hydrant and a wet barrel hydrant are not even close.

Reply
Jesse
6/27/2025 02:34:36 pm

Prior to working in fire protection engineering and loss control, I was a career Firefighter / Medic for 19 years. I would really, really not like this idea. Wrapping the hydrant alone to lay LDH supply line could be a train wreck.

Further, I don't know why we would want to do that. We would have an NRS valve near the base on the lead-in from the main. If this gate valve is in lieu of the NRS valve and this is a wet hydrant, how doest the water get shut off if it gets taken out by a car?

Reply
CESAR LIRA
6/27/2025 02:40:34 pm

Completely agree

Reply
Ryan Hinson
7/2/2025 11:26:58 am

Some responses above appear to be confused as to the indicated type of hydrant. The hydrant in question is a wet-barrel (Jones 3760-series) hydrant. This hydrant type has no vertical 'stem' from a top nut to a base valve (dry-barrel) since, by definition, this hydrant is flooded and under pressure with each individual hose connection valves necessarily preventing water flow. There is therefore, no intrinsic internal universal hydrant 'control' (shutoff) valve in the base of this configuration...which must be on the minimum 6" supply line per NFPA 24 (2022) Section 7.1.1.1. There is also no automatic drain in the bottom of a wet-barrel.

The required hydrant control valve upstream of a hydrant (wet or dry) per NFPA 24 Section 7.1.1.2, must be provided some other way. This could be either with an OS&Y (as shown), other listed valve type, upstream PIV, or valve box...within the allotting 20-ft spacing indicated as AHJ-allowed.

Hence, there is no 'NFPA 24' issue with this configuration as long as there is some type of hydrant isolation control valving (allows for the wholesale replacemenbt of the hydrant without shutting off the upstream water system that I am aware of.

As further-indicated above, there are other reasons why this configuration may not be allowed or preferred due to access/protection issues around the hydrant...depending on ERT SOP tactics.

Personally, I only see the indicated configuration in controlled-access facilities where there is no freezing concern and where specifically coordinated with the ERT. If not in a controlled-access facility, I suggest installing an upstream valve box in to satisfy the NFPA 24 isolation requirement (which it sounds like this owner didn't want). Either way, owner preference must be vetted with the responding entity.

As was already stated, coverage from this hydrant configuration is not affected but access and maneuverability immediately adjacent to it might be.

A separate upstream control/shutoff valve is required either way for the hydrant per NFPA 24. If the concern is vehicular mechanical damage, than either bollards or a traffic-rated dry-barrel hydrant is recommended in lieu of this 'allowed' abovegrade OS&Y configuration.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT