|
When connecting a FDC to a system at a point other than the riser, is it acceptable to connect a 4 x 2½ x 2½ (2-inlet) FDC using 4" pipe feed for the FDC and tying the 4" pipe to a 2" sprinkler main?
Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Glenn Berger
5/5/2025 08:12:36 am
Connecting a 4 inch FDC into a 2 inch pipe does not seem to meet its intent.
Reply
Chad
5/5/2025 08:16:37 am
We allow a single 2 1/2 for small systems…. i’d run it by the AHJ
Reply
Todd E Wyatt
5/5/2025 08:29:10 am
Per the referenced standard (e.g. NFPA 13 - 2022), the size of the FDC shall meet ONE of the (3)16.12.4 requirements :
Reply
J.H.
5/5/2025 08:42:37 am
Here also are some (NFPA 13, 2019 Ed.) restrictions on FDC connection to the system:
Reply
Casey Milhorn
5/5/2025 08:59:04 am
Nothing wrong with it, but worth asking the AHJ if they prefer a 2-1/2" single snoot or siamese connection in a case like this. I've ran into a couple AHJs that still want the siamese for redundancy. The cost difference is fairly negligible since the single snoots aren't that common. I personally like the idea of the siamese connection to keep things standardized and due to the negligible cost difference.
Reply
NK
5/5/2025 09:47:40 am
It's not spelled out in NFPA 13, but we always make sure that there is a piping path from the FDC to the system riser that meets the minimum requirements of 16.12.4. I think 16.12.5.1.1 was added to make sure people weren't connecting 4" FDCs to smaller branchlines which implies the minimum pipe size from the FDC to the system riser should be maintained.
Reply
NK
5/5/2025 09:51:17 am
To be more specific for your question: "When connecting a FDC to a system at a point other than the riser, is it acceptable to connect a 4 x 2½ x 2½ (2-inlet) FDC using 4" pipe feed for the FDC and tying the 4" pipe to a 2" sprinkler main?"
Reply
ANTHONY
5/5/2025 10:06:46 am
If the main, the whole way from the riser is 2'' then I find this to be acceptable. If there is any point on that main that is less than 2'' then you'll need to take 4'' feed back to that point. For instance, if you have a 3'' main for 40 ft with 3 branch lines off it then you'll need to tire back at the 3'' main.
Reply
Pete H
5/5/2025 10:11:19 am
Todd Wyatt nailed it:
Reply
Jack G
5/5/2025 02:12:14 pm
So are we saying the size of the largest main is 2” ? Like a 2 x 2 x 1.25 grid ? And the fdc is on the back main ?
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Dec '25 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
January 2026
PE PREP SERIES |
RSS Feed
