I have a class IV product stored in a HDPE hard body package. With the changes from NFPA 13 2016, edition to the 2025 edition, there are significant changes to the ability to store Group A plastics in legacy warehouses.
What compliance strategies are available to the FP community to remain in compliance while storing in these legacy buildings? A typical warehouse I'll see will have K16.8 @52 psi. This used to be acceptable for group A, but now it is not an option per the newer standard. Typically we're looking at structures over 35 ft. Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments
Pete H
12/11/2025 06:36:22 am
Expanded or Nonexpanded Group A?
Reply
Chad
12/11/2025 08:03:05 am
There are no good compliance options for "legacy" buildings once the storage use changes from the original design. Often its a pump, and occasionally a tank. Not to mention bigger pipe throughout. Especially with taller structures.
Reply
Blaine
12/11/2025 08:10:09 am
Has anyone seen any testing for the hard shell boxes like pelican, Hardigg, or the like. Given their shape and characteristics, I’ve wondered if they behave differently than other plastics. I see a lot of military equipment stored in these transport containers, often incorrectly.
Reply
Glenn Berger
12/11/2025 08:15:46 am
There are no one size fits all solutions when needing to bring existing sprinkler system up to compliance with current standards.
Reply
Brett
12/11/2025 08:16:49 am
NFPA 13 isn't retroactive so if you aren't changing your operations or commodities stored then most jurisdictions won't make you re-evaluate your storage just because there's a new edition of NFPA 13 out.
Reply
Brett
12/11/2025 08:17:37 am
Meant to say two schemes that allow 30 ft vertical spacing of in-racks *with no horizontal barriers*.
Reply
NK
12/11/2025 08:19:16 am
Great question. Huge Issue.
Reply
Jesse
12/11/2025 08:26:44 am
There aren't a lot of great options.
Reply
Robert Morgan
12/11/2025 09:17:02 am
A am the Fire Marshal of a small suburb of a metropolitan area and we have numerous mega warehouses (20+) that are always changing tenants and storage commodities and configurations. Unfortunately, we/I do not have the level of expertise (or often even know when things change in these buildings), to evaluate and determine if the sprinkler protection is adequate. The new changes requiring larger K-factors to adequately protect the materials in legacy buildings are an issue that is not easy to solve. If you could formerly store the same items/configuration in that building, how do we navigate this and tell them they no longer can without an expensive system upgrade.
Reply
Chad
12/11/2025 10:10:44 am
As others stated, NFPA 13 is not retroactive. If it was properly designed for a particular commodity and arrange, you can continue to use it for that same commodity and arrangement.
Reply
Jack G
12/11/2025 10:28:57 am
All municipalities have this catch phase similar to NFPA 1. Easy when going from high piled storage down to ordinary or light hazards but difficult in the other direction.
Reply