I'm seeing a lot of new gymnasiums go up in my state. The architect's drawings show sprinklers under the bleachers.
What does code speak to on sprinklers under bleachers? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments
Ed Kramer
10/15/2026 08:18:33 am
A quick text search in the 2021 IBC for the term 'bleacher': see section 903.2.1.5.1. Then, determine the occupancy beneath - is it light hazard (no potential for storage), or ordinary hazard (likely to have storage). If a different building code is enforced in your area, you could text search it.
Reply
Todd Wyatt
10/15/2026 08:33:12 am
IBC-2024 references the same ... 903.2.1.5.1 (Spaces under grandstands or bleachers) :
Reply
Jack G
10/15/2026 08:58:01 am
NFPA 13 does not inherenty mandate fire sprinklers under mobile or telescoping bleachers by default, because they move and are not fixed in place structural obstructions.
Reply
RWS
10/15/2026 11:27:44 am
Gymnasiums are considered A-4 occupancies and not A-5 occupancies as they are for indoor events.
Reply
Mark Harris
10/15/2026 11:46:55 am
Jack and RWS bring up great points. But I would not consider this the same as an overhead door as an overhead door can still be closed with storage under the open door. Been a long time since I was in my high school gym but don't think you could "close" the bleachers if somebody put something under them so at least my gym did not make sense for storage. If for some reason could store in an area close to wall a line of sprinkler may be warranted.
Reply
Dave
10/15/2026 01:13:36 pm
I agonized over this on a slew of HS's I've been doing. NFSA in general supports the idea that moveable bleachers are a temporary obstruction, thus does not require protection. On the other hand, in the 2025 NFPA 13 on NFPALink, it has an "Ask the AHJ" opinion that states, " Although bleachers are typically movable, they are a permanent part of the space and need to have protection underneath per 9.5.5.3.1 where they are more than 4 ft (1.2 m) wide from the wall when extended. This is similar in nature to the overhead door obstruction mentioned in 10.3.4.1.7." So how do I do that, Sherlock? I've seen sidewalls employed. On a few of my schools it did create an obstruction in the closed position, in which case we added a row of sprinklers against the wall, safe from impact of the mechanism.
Reply