MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Cause of Major Sprinkler Corrosion in Warehouse?

7/29/2025

12 Comments

 
Looking for education on the cause of major sprinkler corrosion in a warehouse.

A general warehouse with ESFR heads has a serious corrosion problem on approximately 600 sprinklers, with two inadvertent actuations occurring in the past 6 months. The image is of the worst corroded sprinkler. Others are more lightly corroded, each with a green hue.

The actuated heads were sent to UL for evaluation as well as non-fused corroded heads. Tests indicated the heads functioned within normal range, with one head slightly delayed. The manufacturer confirmed the heads are not counterfeit.
Picture
The conditions within the warehouse were unique for approximately 7 years, with very high internal temperatures occurring during the winter months, using once-through heating to ensure forklift exhaust CO ppm levels were kept low.

In addition to elevated temperatures, the warehouse received insect fogging applications as normal practice for stored seed and beans. Fogging has also occurred at other similar warehouses, and no problems have been observed at those locations.

Corrosion is on approximately 15% of all sprinklers in the warehouse building area.

Are there similar experiences with corrosion that is similar to the image?

If so, what was determined to be the primary cause? Heat, chemical, or something else?

All of the corroded sprinklers were replaced with new heads and NFPA guidance was observed for temperature selection near forced air heaters.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Pete H
7/29/2025 06:09:52 am

No similar experience:

I assume the 15% were in the same part of the warehouse?

Is this fed from an aquafer or something else that might have microorganisms?

Reply
Joseph Terranova
7/29/2025 08:09:23 am

It appears to be a chloride reaction with some dust accumulation. The pattern and coloration is similar to what is found in pool filtration rooms.

Reply
Chris Logan link
7/29/2025 08:09:28 am

With no obvious environmental concerns, I would check and see if there is electrical ground on the sprinkler system somewhere.

Reply
Glenn Berger
7/29/2025 08:20:48 am

Need to review the chemicals involved with the "insect fogging" application mentioned the write-up.

Reply
Jesse
7/29/2025 08:25:39 am

This is a fascinating one.

Its ESFR so I'm presuming there isn't a manufacturing process in close proximity that would produce corrosive off-gassing. Chris's comment re: an electrical ground is interesting but I would think more widespread than 15% of the sprirnklers.

I wonder if these 15% of sprinklers affected are contiguous to one area of the system(s), or if these are spread throughout.

I'm gonna follow this post today. Hopefully Dann or Glenn or Franck or anyone of you guys much smarter than I have some insight!

Reply
Franck
7/29/2025 08:29:52 am

Could it be related to the products stored in the warehouse ?
Just a guess...
If you had seed and beans in a bulk storage configuration, it could be that dust (generated by transferring the product) from seed and beans could accumulate on the sprinklers, thus having moisture (if the area was heated, the seed and beans would release water by evaporation) accumulated at the same place to increase the corrosion level.
More obvious on sprinklers as this is where the dust tends to accumulate easily compared to piping (that are painted in addition to limit outside corrosion).

Reply
Chad
7/29/2025 08:42:08 am

I too wonder what the products are off gassing. Its most likely environmental, possibly whatever they fog it with.

It possible but less likely its the water or its being used as a ground

Reply
Dan Wilder
7/29/2025 08:29:54 am

So brass & bronze will corrode green with both chemical and humidity factors. As you stated this is a seed and bean warehouse the chemical factor (typically chlorine) decreases dramatically, however with a high humidity level kept for most of these warehouses, this is more likely the cause. Due to the more uniform rusting on the pipe, the warm humid air rising within the structure will naturally condense on the pipe as shown.

What is the proximity of the units that heat/cool/humidify the air to the effected sprinklers? What about exhaust fan and high points in the roof compared to the corrosion of the sprinklers? What do the hangers look like?

Reply
Jack G
7/29/2025 08:49:45 am

I think Chris s explanation of electrical, ( I think the building is not grounded properly ) is the major problem, along with the chemical fogging, the ionization of corrosive particals.,

Reply
Jeff Ayers
7/29/2025 10:17:33 am

I had a garage in Baltimore with similar corrosion problems.
The cause for the corrosion and deterioration (more than 50%) was MIC.
https://c1sinc.com/blog/mic-microbiologically-influenced-corrosion-fire-sprinkler-pipes
Microbilogically influenced corrosion: "MIC in fire protection systems can be described as a chemical corrosion process that is concentrated and accelerated by the activity of specific bacteria within a fire-sprinkler system resulting in the premature failure of metallic system components."

The problem was the water supply (supposedly).
The problem was exacerbated by the sprinkler did not have positive fall for drainage at all mains and branches. But the upright heads (it was a dry system in the garage) corroded just as much as the pendant heads in the BOH rooms.

Reply
Greg
8/1/2025 08:23:14 am

Thank you for the insight. All responses have been very helpful and prompted further evaluation of makeup air entering the building.

The following corrosion coupon is being considered for the evaluation.

https://corrosionmonitor.com/products/corrosion-classification-coupon-plus

Reply
Greg
8/15/2025 03:02:32 pm

Also, we verified that a fumigant containing phosphine products was not used in the warehouse's history. Phosphine containing fumigants have been known to cause metal corrosion.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT