|
We have a consultant showing a 6" wet sprinkler riser routing through the 1st floor of a building, supplying sprinklers, then heading to a stairwell to supply a wet manual standpipe. I am confident that supplying a standpipe downstream of a sprinkler system is not allowed, as there would be no way to fight the fire with hoses without the ability to shut off the sprinkler system, but keep the standpipe live.
Can someone shed some light on the code referring to this in either NFPA 13, 14, or even FM Global that details standpipes can feed sprinkler systems in a combination setup, but a sprinkler system cannot feed a standpipe? Thanks in advance! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Josh
3/30/2026 08:14:25 am
If you shut off sprinklers to level 1, it sounds like you're shutting off standpipes too in this configuration unless there's something I'm missing.
Reply
Jesse
3/30/2026 08:26:51 am
Combined SP and AS systems aren't new, but as I read this; it seems the issue is the SP being downstream of the AS system. That SP riser in the stairwell should be fed by the AS main.
Reply
Chris
3/30/2026 08:35:47 am
The code does permit combined systems, but it does not clearly define in detail what constitutes a “combined system.” Because of that, the solution you mentioned above could be considered code-compliant depending on the reviewer’s interpretation.
Reply
Glenn Berger
3/30/2026 08:38:43 am
Your concerns are valid. Combined supply to sprinklers and standpipe is okay, but requires separated controls. Your comment did not indicate if the standpipe system was a Class I or Class II, or Class III.
Reply
Declan
3/30/2026 11:56:00 pm
Standpipes are all class I for this building. Furthermore, the fire protection for the building is fed from 4 systems in a riser room which ironically also has a 4” bulk main feeding 2 of the total 4 standpipes. The other 2 standpipes are being fed downstream of 2 of the sprinkler system risers.
Reply
Brett
3/30/2026 09:12:26 am
Is it truly a standpipe or are there just hose valves supplied by the sprinkler system?
Reply
Dan Wilder
3/30/2026 10:20:41 am
Chapter 5 of NFPA 14 indicates that for a manual standpipe system it shall have an approved water supply. None of those indicate that a sprinkler system can be a distribution point and while a standpipe is defined as "System piping that delivers the water supply for hose connections, and for sprinklers on combined systems, from floor to floor" (3.3.27), there is no definition of a sprinkler system being able to perform the same duty.
Reply
Declan
3/31/2026 12:00:57 am
Thank you for the references. I also agree that the standard is not explicit in stating sprinkler systems cannot feed standpipes, just that standpipes can feed sprinkler systems and it’s taken as an industry standard that one follows the other and cannot be the other way around.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop April '26 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
April 2026
PE PREP SERIES |
RSS Feed
